+TL=-15; // Source temperature in degree celcius
+TH=40; // Sink temperature in degree celcius
+// From the table of properties of Freon - 12
+h3=74.53; h1=180.85; h4=h3; // specific enthalpy in kJ/kg
+s1=0.7046; s2=0.682; // specific entropy in kJ/kg K
+// (a)
+// (i).Condensor and Evaporator pressure
+pc=0.9607; // Saturation pressure at TH in MPa
+pE=0.1826; // Saturation pressure at TL in MPa
+disp ("MPa",pE,"Evaporator pressure = ","MPa",pc,"Condensor pressure = ","(i).Condensor and Evaporator pressure","(a)");
+// (ii).Compressor discharge temperature & Enthalpy
+p2=pc; // Condensor pressure
+s2=s1; // refer figure 8.25
+// From the table of properties of Freon - 12 at pc
+t2=46.8; // Compressor discharge temperature in degree celcius
+h2=208.3; // specific enthalpy in kJ/kg
+disp ("kJ/kg",h2,"Enthalpy = ","oC",t2,"Compressor discharge temperature = ","(ii).Compressor discharge temperature & Enthalpy");
+// (iii).Ratio of COP of the cycle to Carnot COP
+w=h2-h1; // Compressor work
+qL=h1-h4; // Refrigeration effect
+COP=qL/w; // COP of the cycle
+COPc=4.68; // COP of carnot cycle from example 8.7
+r=COP/COPc; // Ratio of COP of the cycle to Carnot COP
+disp (r,"(iii).Ratio of COP of the cycle to Carnot COP = ");
+// (b)
+QL=0.440; // Capacity of refrigerator in kW (1/8 ton of refrigeration)
+m=QL/qL; // Mass flow rate of refrigerant
+W=m*w; // Power consumption of compressor
+QH=QL+W; // Heat rejected
+disp ("kW",QH,"Heat rejected to surroundings = ","kW",W,"Power consumption of compressor = ","kg/s",m,"Mass flow rate of refrigerant = ","(b)");
|