diff --git a/3888/CH11/EX11.3/Ex11_3.sce b/3888/CH11/EX11.3/Ex11_3.sce new file mode 100644 index 000000000..15433efaa --- /dev/null +++ b/3888/CH11/EX11.3/Ex11_3.sce @@ -0,0 +1,66 @@ +//Electric Power Generation, Transmission and Distribution by S.N.Singh
+//Publisher:PHI Learning Private Limited
+//Year: 2012 ; Edition - 2
+//Example 11.3
+//Scilab Version : 6.0.0 ; OS : Windows
+
+clc;
+clear;
+
+
+P=50; //Power of the line in MW
+l=100; //Length of the line in km
+pf=0.8; //Power factor
+V=132; //Voltage of the line in kV
+R=0.1; //Resistance of the conductor in Ohm/km
+X=0.3; //Reactance of the conductor in Ohm/km
+y=3*10^(-6); //Admittance of the conductor in mho/km
+Vr=V/(3)^(1/2); //Receiving end voltage in kV
+Z=(R+%i*X)*100; //Series impedance in Ohm
+Y=(0.0+%i*y)*100; //Shunt admittance on mho
+Ir=P*10^(3)/(3*Vr*pf); //Receiving end current in A
+Vc=Vr*(pf+%i*0.6)+(Ir*Z/2)*10^(-3); //Capacitance voltage in kV
+Ic=Y*Vc*10^(3); //Shunt branch current in A
+Is=Ic+Ir; //Sending end current in A
+Vs=Vc+(Is*Z/2)*10^(-3); //Sending end voltage in kV
+Vsl=abs(Vs)*3^(1/2); //Line to line sending end voltage in kV
+pf1=cos(atan(imag(Vs),real(Vs))-atan(imag(Is),real(Is))); //Sending end power factor
+Vr1=abs(Vs)/(1+(Z*Y/2)); //Receiving end voltage at no_load in kV
+reg=((abs(Vr1)-Vr)/Vr)*100; //Regulation of the line
+eff=P*10^(6)/(P*10^(6)+3*((abs(Is)^(2)*R*l)/2+(Ir^(2)*R*l)/2))*100; //Efficiency of the line
+Ic1=(Y/2)*Vr*10^(3); //Capacitance 1 current in A
+Il=Ir*(0.8-%i*0.6)+Ic1; //Line current in A
+Vs1=Vr+Il*Z*10^(-3); //Sending end voltage in kV
+Vsl1=abs(Vs1)*3^(1/2); //Line to line sending end voltage in kV
+Ic2=((Y/2)*Vs1*10^(3)); //Capacitance 2 current in A
+Is1=Il+Ic2; //Sending end current in A
+pf2=cos(atan(imag(Vs1),real(Vs1))-atan(imag(Is1),real(Is1))); //Power factor
+V=abs(Vs1)/(1+(Z*Y/2)); //Receiving end voltage at no_load in kV
+reg1=((abs(V)-Vr)/Vr)*100; //Regulation of the line
+eff1=(P*10^(6)/(P*10^(6)+3*(abs(Il)^(2)*R*l)))*100; //Efficiency of the line
+
+
+printf("\nnominal-T method");
+printf("\nSending end voltage of the line %.2f kV",Vsl);
+printf("\nSending end powerfactor of the line %.3f",pf1);
+printf("\nEfficiency of the line %.2f percentage",eff);
+printf("\nRegulation of the line %.2f percentage",reg);
+printf("\nnominal-pi method");
+printf("\nSending end voltage of the line %.2f kV",Vsl1);
+printf("\nSending end powerfactor of the line %.3f",pf2);
+printf("\nEfficiency of the line %.2f percentage",eff1);
+printf("\nRegulation of the line %.2f percentage",reg1);
+ //Variation present in result due to wrong calculation of Ic2 value
+
+
+
+
+
+
+
+
+
+
+
+
+
|