diff --git a/3872/CH3/EX3.7/Ex3_7.jpg b/3872/CH3/EX3.7/Ex3_7.jpg Binary files differnew file mode 100644 index 000000000..6a438e9af --- /dev/null +++ b/3872/CH3/EX3.7/Ex3_7.jpg diff --git a/3872/CH3/EX3.7/Ex3_7.sce b/3872/CH3/EX3.7/Ex3_7.sce new file mode 100644 index 000000000..a64cf057e --- /dev/null +++ b/3872/CH3/EX3.7/Ex3_7.sce @@ -0,0 +1,42 @@ +//Book - Power system: Analysisi & Design 5th Edition
+//Authors - J. Duncan Glover, Mulukutla S. Sarma, and Thomas J.Overbye
+//Chapter-3 ;Example 3.7
+//Scilab Version - 6.0.0; OS - Windows
+
+clc;
+clear;
+
+Sr=400 //rated power of transformer in MVA
+VT1p=13.8 // rated voltage of transformer primary side in kV
+VT1s=199.2 // rated voltage of transformer secondary side in kV
+Xeq=0.10 // leakage reactance of transformer in Ohms
+Sa=1000 //High voltage side absorbs power in MVA
+pf=0.90 // lagging power factor
+VANH=199.2
+Sb=1200 //base power in MVA
+VbHLL=345 //Hihg volgage side lini to line base voltag in kV
+IbH=1200/(345*sqrt(3)) //high voltage side base current in Amperes
+
+VAN=1.0 //per unit load voltage
+Theta=acos(0.9)
+IA=((1000/(345*(sqrt(3))))/2.008)*(exp(%i*(-Theta))) //Per unit load current
+Van=VAN+(%i*Xeq)*IA // voltage at low voltage bus
+VbXLN1=13.8
+Van1L=Van*VbXLN1 //low voltage wye winding in kV
+Ean=(exp(%i*(-30)*(%pi/180)))*VAN //source voltage in per unit
+Ia=(exp(%i*(-30)*(%pi/180)))*IA //source current in per unit
+Van2=Ean+(%i*Xeq)*Ia
+VbXLN2=13.8/(sqrt(3))
+Van2L=Van2*VbXLN2 //low voltage delta winding in kV
+
+printf('The magnitude of voltage at low voltage bus(star) in per unit is %.4f and its angle is %.4f degrees\n',abs(Van),atand(imag(Van),real(Van)));
+printf('The magnitude of low voltage star winding in kV is %.4f kV and its angle is %.4f degrees\n',abs(Van1L),atand(imag(Van1L),real(Van1L)));
+printf('The magnitude of voltage at low voltage bus(delta) in per unit is %.4f and its angle is %.4f degrees\n',abs(Van2),atand(imag(Van2),real(Van2)));
+printf('The magnitude of low voltage delta winding in kV is %.4f kV and its angle is %.4f degrees\n',abs(Van2L),atand(imag(Van2L),real(Van2L)));
+
+
+
+
+
+
+
|