+clc
+P1 = 2.4 //Compressor inlet pressure in bar
+T1 = 0 // Compressor inlet temperature in degree Celsius
+h1 = 188.9 // Enthalpy of refrigerant at state 1 in kJ/kg
+s1 = 0.7177 // Entropy of refrigerant at state 1 in kJ/kgK
+v1 = 0.0703 // Specific volume at state 1 in m^3/kg
+P2 = 9 // Compressor outlet pressure in bar
+T2 = 60 // Compressor outlet pressure in degree Celsius
+h2 = 219.37 // Actual compressor outlet enthalpy in kJ/kgK
+h2s = 213.27 // Ideal compressor outlet enthalpy in kJ/kgK
+h3 = 71.93 // Enthalpy of refrigerant at state 3 in kJ/kg
+h4 = h3 // Isenthalpic process
+
+A1V1 = 0.6/60 // volume flow rate in kg/s
+m_dot = A1V1/v1 // mass flow rate
+Wc_dot = m_dot*(h2-h1) // Compressor work
+Q1_dot = m_dot*(h2-h3) // Heat extracted
+COP = Q1_dot/Wc_dot // Coefficient of performance
+nis = (h2s-h1)/(h2-h1) // Isentropic compressor efficiency
+printf("\n Example 14.10\n")
+printf("\n Power input is %f kW",Wc_dot)
+printf("\n Heating capacity is %f kW",Q1_dot)
+printf("\n COP is %f",COP)
+printf("\n The isentropic compressor efficiency is %f percent",nis*100)
+//The answers vary due to round off error
+
diff --git a/3685/CH14/EX14.10/Ex14_10.txt b/3685/CH14/EX14.10/Ex14_10.txt
new file mode 100644
index 000000000..09d8c898a
--- /dev/null
+++ b/3685/CH14/EX14.10/Ex14_10.txt
@@ -0,0 +1,7 @@
+
+ Example 14.10
+
+ Power input is 4.334282 kW
+ Heating capacity is 20.972973 kW
+ COP is 4.838858
+ The isentropic compressor efficiency is 79.980309 percent \ No newline at end of file