+// A Texbook on POWER SYSTEM ENGINEERING
+// A.Chakrabarti, M.L.Soni, P.V.Gupta, U.S.Bhatnagar
+// DHANPAT RAI & Co.
+// SECOND EDITION
+
+// PART II : TRANSMISSION AND DISTRIBUTION
+// CHAPTER 3: STEADY STATE CHARACTERISTICS AND PERFORMANCE OF TRANSMISSION LINES
+
+// EXAMPLE : 3.1 :
+// Page number 127-128
+clear ; clc ; close ; // Clear the work space and console
+
+// Given data
+P = 2.0*10**6 // Power delivered(W)
+V_r = 33.0*10**3 // Receiving end voltage(V)
+PF_r = 0.8 // Receiving end lagging power factor
+R = 10.0 // Total resistance of the line(ohm)
+X = 18.0 // Total inductive resistance of the line(ohm)
+
+// Calculations
+// Case(i)
+I = P/(V_r*PF_r) // Line current(A)
+sin_phi_r = (1-PF_r**2)**0.5 // Sinφ_R
+V_s = V_r+I*R*PF_r+I*X*sin_phi_r // Sending end voltage(V)
+reg = (V_s-V_r)/V_r*100 // Voltage regulation(%)
+// Case(ii)
+PF_s = (V_r*PF_r+I*R)/V_s // Sending end lagging power factor
+// Case(iii)
+loss = I**2*R // Losses(W)
+P_s = P+loss // Sending end power(W)
+n = P/P_s*100 // Transmission efficiency(%)
+
+// Results
+disp("PART II - EXAMPLE : 3.1 : SOLUTION :-")
+printf("\nCase(i) : Percentage voltage regulation = %.3f percent", reg)
+printf("\nCase(ii) : Sending end power factor = %.2f (lag)", PF_s)
+printf("\nCase(iii): Transmission efficiency, η = %.2f percent \n", n)
+printf("\nNOTE: ERROR: pf is 0.8 and not 0.9 as mentioned in the textbook problem statement")