summaryrefslogtreecommitdiff
path: root/Working_Examples/83/CH12/EX12.2
diff options
context:
space:
mode:
authorSiddharth Agarwal2019-09-03 18:27:40 +0530
committerSiddharth Agarwal2019-09-03 18:27:40 +0530
commit8ac15bc5efafa2afc053c293152605b0e6ae60ff (patch)
treee1bc17aae137922b1ee990f17aae4a6cb15b7d87 /Working_Examples/83/CH12/EX12.2
parent52a477ec613900885e29c4a0b02806a415b4f83a (diff)
downloadXcos_block_examples-master.tar.gz
Xcos_block_examples-master.tar.bz2
Xcos_block_examples-master.zip
Xcos examples from textbooks and for blocksHEADmaster
Diffstat (limited to 'Working_Examples/83/CH12/EX12.2')
-rwxr-xr-xWorking_Examples/83/CH12/EX12.2/example_12_2.sce45
-rwxr-xr-xWorking_Examples/83/CH12/EX12.2/result_example_12_2.txt7
2 files changed, 52 insertions, 0 deletions
diff --git a/Working_Examples/83/CH12/EX12.2/example_12_2.sce b/Working_Examples/83/CH12/EX12.2/example_12_2.sce
new file mode 100755
index 0000000..198bc31
--- /dev/null
+++ b/Working_Examples/83/CH12/EX12.2/example_12_2.sce
@@ -0,0 +1,45 @@
+//Chapter 12
+//Example 12.1
+//page 448
+//To calculate steady state power limit
+clear;clc;
+
+Xdg=1*%i; //generator's
+Xdm=1*%i; //motor's
+Xt=0.1*%i; //transformers
+Xl=0.25*%i; //transmission line's
+Xc=-1*%i; //static capacitor's
+Xi=1*%i; //inductive reactor
+Eg=1.2; //generator's internal voltage
+Em=1; //motor's internal voltage
+
+//case(i) steady state power limit without reactor
+P1=(abs(Eg)*abs(Em))/(abs(Xdg+Xt+Xl+Xt+Xdm));
+printf('\n\n Steady state power limit without reactor = %0.5f pu',P1);
+
+//case(ii) steady state power limit with capacitive reactor
+//three arms of star connected reactances are
+Xa=Xdg+Xt+Xl; //from generator side
+Xb=Xdm+Xt; //from load side
+Xc=Xc; //from reactor side
+
+//converting star to delta
+//reactance between generator side to load side is
+Xab=(Xa*Xb+Xb*Xc+Xc*Xa)/Xc;
+//power limit is
+P2=(abs(Eg)*abs(Em))/(abs(Xab));
+printf('\n\n Steady state power limit with capacitive reactor = %0.5f pu',P2);
+
+//case(iii) steady state power limit with inductive reactor
+//three arms of star connected reactances are
+Xa=Xdg+Xt+Xl; //from generator side
+Xb=Xdm+Xt; //from load side
+Xc=Xi; //from reactor side
+
+//converting star to delta
+//reactance between generator side to load side is
+Xab=(Xa*Xb+Xb*Xc+Xc*Xa)/Xc;
+//power limit is
+P3=(abs(Eg)*abs(Em))/(abs(Xab));
+printf('\n\n Steady state power limit with inductive reactor = %0.5f pu',P3);
+
diff --git a/Working_Examples/83/CH12/EX12.2/result_example_12_2.txt b/Working_Examples/83/CH12/EX12.2/result_example_12_2.txt
new file mode 100755
index 0000000..20581cd
--- /dev/null
+++ b/Working_Examples/83/CH12/EX12.2/result_example_12_2.txt
@@ -0,0 +1,7 @@
+
+
+ Steady state power limit without reactor = 0.48980 pu
+
+ Steady state power limit with capacitive reactor = 1.24352 pu
+
+ Steady state power limit with inductive reactor = 0.30496 pu