//Chapter 3
//Example 3.2
//page 88
//To claculate the capacitance to neutral and charging current of a three phase transmission line
clear;clc;
d=350; //distance between adjacent lines
r=1.05/2; //radius of the conductor
v=110e3; //line voltage;
f=50;
Deq=(d*d*2*d)^(1/3); //GMD or equivalent
Cn=(0.0242/log10(Deq/r));
Xn=1/(2*%pi*f*Cn*10^(-6)); // Cn is in uF hence we add 10^6 while printing
Ic=(v/sqrt(3))/Xn;
printf("\nCapacitance to neutral is = %f uF/km\n\n",Cn);
printf("Capacitive rectance of the line is = %f ohm/km to neutral\n\n",Xn);
printf("Charging Current = %0.2f A/km\n\n",Ic);
|