sequence impedances are given by 
Z1=j0.1599 
Z2=j0.1599 
Z0=j1.7120

Fault Current= -j1.3422

Components currents flowing from Generator and motor are 
Ig1= -j0.1363 
Ig2= -j0.1363 
Ig0=0

Im1= -j0.3111 
Im2= -j0.3111 
Im0= -j0.4474

Fault current from the generator towards g are  
  - 0.2725981i  
    0.1362990i  
    0.1362990i  
and to g from motors are 
  - 1.0696512i  
  - 0.1362990i  
  - 0.1362990i  

Positive sequence current =-0.136 pu
Negative sequence current =0.136 pu
Zero sequence current=0

The per unit motor currents are:
Motor1:0.66 +j0.495 pu
Motor2:0.33 +j0.247 pu

Voltage behind subtransient reactances:
Motor1:Em1= 1.0798-j0.2278
Motor2:Em2= 1.0798-j0.2278
Generator:Eg= 0.5193j+0.5199

The actual value of positive sequence current from the generator towards fault is = 0.99+j0.606
The actual value of positive sequence current from the motors towards fault is = -0.99-j1.054