example 10.1
minimum load ic is
ic of unit1 =ic of unit2 when unit2=20MW and unit1=65MWload division
for plant ic 50MW then p1 is 100MW plant2 is 66MW and total is 166MW
for plant ic 55MW then p1 is 125MW plant2 is 100MW and total is 225MW
for plant ic 60MW then p1 is 150MW plant2 is 133MW and total is 283MW
for plant ic 65MW then p1 is 175MW plant2 is 166MW and total is 341MW
for plant ic 70MW then p1 is 200MW plant2 is 200MW and total is 400MW
for plant ic 75MW then p1 is 225MW plant2 is 233MW and total is 458MW
for plant ic 77.5MW then p1=237MW p2 =250MW
for plant ic 80MW then p1 is 250MW plant2 is 250MW and total is 500MW
|