//Book - Power System: Analysis & Design 5th Edition
//Authors - J. Duncan Glover, Mulukutla S. Sarma, and Thomas J. Overbye
//Chapter - 8 ; Example 8.8
//Scilab Version - 6.0.0 ; OS - Windows
clc;
clear;
Vp = [277; 260*(cos(-120*%pi/180)+%i*sin(-120*%pi/180)); 295*(cos(115*%pi/180)+%i*sin(115*%pi/180))]; //given column vector of phase voltage in volts
Zl1 = 0.087+%i*(0.99); //impedace of line 1 in ohm
Zdel = 22.98+%i*(19.281); //impedance of the delta load in ohm
Zl2 = 0.087+%i*(0.99); //impedance of line 2 in ohm
function [Vp1]=phaseshift(x1,x2)
[r theta]=polar(x1);
Vp1=r*(cos(theta+x2*%pi/180)+%i*sin(theta+x2*%pi/180));
endfunction
V0 = (Vp(1,1)+Vp(2,1)+Vp(3,1))/3; //zero sequence voltage in V
V1 = (Vp(1,1)+phaseshift(Vp(2,1),120)+phaseshift(Vp(3,1),240))/3; //positive sequence voltage in V
V2 = (Vp(1,1)+phaseshift(Vp(2,1),240)+phaseshift(Vp(3,1),120))/3; //negative sequence voltage in V
I0 = 0; //zero sequence current in A
I1 = V1/(Zl1+(Zdel/3)); //positive sequence current in A
I2 = V2/(Zl2+(Zdel/3)); //negative sequence current in A
Ia = I0+I1+I2; //zero source current in A
Ib = I0+phaseshift(I1,240)+phaseshift(I2,120); //positive source current in A
Ic = I0+phaseshift(I1,120)+phaseshift(I2,240); //negative source current in A
Sp = (Vp(1,1)*(conj(Ia)))+(Vp(2,1)*(conj(Ib)))+(Vp(3,1)*(conj(Ic))); //total complex power delivered to load in VA
Ss = (V0*conj(I0))+(V1*conj(I1))+(V2*conj(I2)); //total complex power delivered to the sequence networks in VA
SS = 3*Ss;
printf('\n 3Ss = %0.2f , Sp = %0.2f ',abs(SS), abs(Sp));
if (ceil(real(SS))==ceil(real(Sp))) then
printf('\n Sp is equal to 3Ss');
else
printf('\n Sp is not equal to 3Ss');
end
|