clear;
clc;
p=50; //power transmits in MW
pf=0.8; //power factor lagging
va=132 //actual voltage in kV
v=132; //KV base
m=100; // MVA base
z=complex(40,100); // transmision impedence
//calculate pu values
zb=(v^2)/m; //impedence base
i=(m*1000)/(sqrt(3)*va); //base current in KA
s=p/(pf*m);
ppu=p/m;
q=(((p/pf)*0.6)/m);
mprintf(" complex power pu= %.3f , active power pu= %.3f , reactive power pu=%.3f \n",s,ppu,q);
vpu=va/v;
mprintf(" kV pu= %.3f\n",vpu);
ia=(p*1000)/(sqrt(3)*va*pf);
ipu=ia/i;
mprintf(" current pu=%.3f \n",ipu);
za=sqrt(((real(z))^2) + ((imag(z))^2));
zpu=za/zb;
rpu=(real(z))/zb;
xpu=(imag(z))/zb;
mprintf(" Impedence pu= %.3f , resistance pu= %.3f , reactance pu=%.3f ",zpu,rpu,xpu);
|