// A Texbook on POWER SYSTEM ENGINEERING
// A.Chakrabarti, M.L.Soni, P.V.Gupta, U.S.Bhatnagar
// DHANPAT RAI & Co.
// SECOND EDITION
// PART II : TRANSMISSION AND DISTRIBUTION
// CHAPTER 10: POWER SYSTEM STABILITY
// EXAMPLE : 10.23 :
// Page number 306
clear ; clc ; close ; // Clear the work space and console
// Given data
G = 20.0 // Rating of turbo-generator(MVA)
PF = 0.75 // Lagging power factor
fault = 0.5 // Fault reduces output power
N_s = 1500.0 // Synchronous speed(rpm). From Example 10.22
// Calculations
P_prefault = PF*G // Pre-fault output power(MW)
P_a = P_prefault*fault // Post-fault output power(MW)
w = 2.0*%pi*N_s/60 // ω(rad/sec)
T_a = P_a*10**6/w // Accelerating torque at the time of fault occurrence(N-m)
// Results
disp("PART II - EXAMPLE : 10.23 : SOLUTION :-")
printf("\nAccelerating torque at the time of fault occurrence, T_a = %.f N-m", T_a)
|