blob: c2ab1d3704001940faa53dd84d425b20edc7103d (
plain)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
|
//CHAPTER 10- THREE-PHASE INDUCTION MACHINES
//Example 12
disp("CHAPTER 10");
disp("EXAMPLE 12");
//VARIABLE INITIALIZATION
v=440; //in Volts
I=1200; //in Amperes
eff=0.85; //full load efficiency
pow_fact=0.8; //full load power factor
//SOLUTION
//solution (a)
I_fl1=I/5; //starting current at rated voltage is 5 times the rated full-load current
p1=sqrt(3)*v*I_fl1*pow_fact*eff;
disp(sprintf("(a) The maximum rating when the motor starts at full voltage is %f kW",p1/1000));
//solution (b)
I_fl2=I/((0.8^2)*5);
p2=sqrt(3)*v*I_fl2*pow_fact*eff;
disp(sprintf("(b) The maximum rating when the motor is used with an auto-transformer is %f kW",p2/1000));
//solution (c)
I_fl3=I/((0.578^2)*5);
p3=sqrt(3)*v*I_fl3*pow_fact*eff;
disp(sprintf("(c) The maximum rating when the motor is used with star-delta starter is %f kW",p3/1000));
//The answers are slightly different due to precision of floating point numbers
//END
|