 Base Current = 836.739521 A
 Subtransient current in line a = -j3586 A 

 
 Symmetrical Components of voltage from point a to ground   

 Va1 = 0.64 per unit
 Va2 = -0.50 per unit
 Va0 = -0.14 per unit 

 
 Line to ground voltages   

 Va = 0.00 /_-180.00 per unit
 Vb = 1.01 /_-102.22 per unit
 Vc = 1.01 /_102.22 per unit 

 
 Line to line voltages in per-unit are   

 Vab = 1.01 /_77.78 per unit
 Vbc = 1.98 /_-90.00 per unit
 Vca = 1.01 /_102.22 per unit 

 
 Line to line voltages in volts   

 Vab = 8.07 /_77.78 kV
 Vbc = 15.77 /_-90.00 kV
 Vca = 8.07 /_102.22 kV