1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
|
// Electric Machinery and Transformers
// Irving L kosow
// Prentice Hall of India
// 2nd editiom
// Chapter 14: TRANSFORMERS
// Example 14-31
clear; clc; close; // Clear the work space and console.
// Given data
S = 500 ; // kVA rating of distribution transformer
// given data from ex.14-20
V_1 = 2300 ; // Primary voltage in volt
V_2 = 208 ; // Secondary voltage in volt
f = 60 ; // Frequency in Hz
// SC-test data
P_sc = 8200 ; // wattmeter reading in W
I_sc = 217.4 ; // Short circuit current in A
V_sc = 95 ; // Short circuit voltage in V
// OC-test data
P_oc = 1800 ; // wattmeter reading in W
I_oc = 85 ; // Open circuit current in A
V_oc = 208 ; // Open circuit voltage in V
LF_1 = 20 ; // Load fraction in percent
LF_2 = 40 ; // Load fraction in percent
LF_3 = 80 ; // Load fraction in percent
LF_fl = 100 ; // rated load in percent
LF_4 = 125 ; // Load fraction in percent
LF1 = 0.2 ; // Load fraction
LF2 = 0.4 ; // Load fraction
LF3 = 0.8 ; // Load fraction
LF4 = 1.25 ; // Load fraction
PF1 = 0.7 ; // power factor
PF2 = 0.8 ; // power factor
PF3 = 0.9 ; // power factor
PF_fl = 1 ; // power factor
PF4 = 0.85 ; // power factor
t1 = 4 ; // period of operation in hours
t2 = 4 ; // period of operation in hours
t3 = 6 ; // period of operation in hours
t_fl = 6 ; // period of operation in hours
t4 = 2 ; // period of operation in hours
// Calculations
// case a
t = 24 ; // hrs in a day
P_c = P_oc ; // wattmeter reading in W (OC test)
W_c = (P_c * t)/1000 ; // COre loss over 24 hour period
// case b
Psc = P_sc/1000 ; // wattmeter reading in W (SC test)
P_loss_1 = (LF1^2)*Psc ; // Power loss in kW for 20% Load
P_loss_2 = (LF2^2)*Psc ; // Power loss in kW for 40% Load
P_loss_3 = (LF3^2)*Psc ; // Power loss in kW for 80% Load
P_loss_fl = Psc ; // Power loss in kW for 100% Load
P_loss_4 = (LF4^2)*Psc ; // Power loss in kW for 125% Load
// energy loss in kWh
energy_loss1 = P_loss_1 * t1 ; // Enegry loss in kWh for 20% Load
energy_loss2 = P_loss_2 * t2 ; // Enegry loss in kWh for 40% Load
energy_loss3 = P_loss_3 * t3 ; // Enegry loss in kWh for 80% Load
energy_loss_fl = P_loss_fl * t_fl ; // Enegry loss in kWh for 100% Load
energy_loss4 = P_loss_4 * t4 ; // Enegry loss in kWh for 125% Load
// Total energy losses in 24hrs
W_loss_total = energy_loss1 + energy_loss2 + energy_loss3 + energy_loss_fl + energy_loss4 ;
// case c
P_1 = LF1*S*PF1 ; // Power output for 20% load
P_2 = LF2*S*PF2 ; // Power output for 40% load
P_3 = LF3*S*PF3 ; // Power output for 80% load
P_fl = S*PF_fl ; // Power output for 100% load
P_4 = LF4*S*PF4 ; // Power output for 125% load
Energy_1 = P_1*t1 ; // Energy delivered in kWh for 20%load
Energy_2 = P_2*t2 ; // Energy delivered in kWh for 40%load
Energy_3 = P_3*t3 ; // Energy delivered in kWh for 80%load
Energy_fl = P_fl*t_fl ; // Energy delivered in kWh for 100%load
Energy_4 = P_4*t4 ; // Energy delivered in kWh for 125%load
// Total energy delivered in 24hrs
W_out_total = Energy_1 + Energy_2 + Energy_3 + Energy_fl + Energy_4 ;
// case d
eta = W_out_total / (W_out_total + W_c + W_loss_total) * 100 ; // All-day efficiency
// Display the results
disp("Example 14-31 Solution : ");
printf(" \n a: Total energy core loss for 24hrs, including 2hours at no-load,");
printf(" \n W_c = %.1f kWh \n ",W_c);
printf(" \n b: From SC test, equivalent copper loss at rated load = %.1f kW, ",Psc);
printf(" \n and the various energy losses during the 24 hr period are tabulated as :\n");
printf(" \n _____________________________________________________________________________________");
printf(" \n Percent Rated load \t Power loss(kW) \t Time period(hours) \t Energy loss(kWh)");
printf(" \n _____________________________________________________________________________________");
printf(" \n\t\t%d \t %f \t\t\t %d \t\t\t %.2f \n ",LF_1,P_loss_1,t1,energy_loss1);
printf(" \n\t\t%d \t %f \t\t\t %d \t\t\t %.2f \n ",LF_2,P_loss_2,t2,energy_loss2);
printf(" \n\t\t%d \t %f \t\t\t %d \t\t\t %.2f \n ",LF_3,P_loss_3,t3,energy_loss3);
printf(" \n\t\t%d \t %f \t\t\t %d \t\t\t %.2f \n ",LF_fl,P_loss_fl,t_fl,energy_loss_fl);
printf(" \n\t\t%d \t %f \t\t\t %d \t\t\t %.2f \n ",LF_4,P_loss_4,t4,energy_loss4);
printf(" \n _____________________________________________________________________________________");
printf(" \n Total energy load losses over 24hour period (excluding 2hrs at no-load) = %.2f ",W_loss_total);
printf(" \n _____________________________________________________________________________________\n\n");
printf(" \n c: Total energy output over the 24 hour period is tabulated as : \n");
printf(" \n _____________________________________________________________________________________");
printf(" \n Percent Rated load \t PF \t kW \t Time period(hours) \t Energy delivered(kWh)");
printf(" \n _____________________________________________________________________________________");
printf(" \n\t\t%d \t %.1f \t %.f \t\t %d \t\t\t %d ",LF_1,PF1,P_1,t1,Energy_1);
printf(" \n\t\t%d \t %.1f \t %.f \t\t %d \t\t\t %d ",LF_2,PF2,P_2,t2,Energy_2);
printf(" \n\t\t%d \t %.1f \t %.f \t\t %d \t\t\t %d ",LF_3,PF3,P_3,t3,Energy_3);
printf(" \n\t\t%d \t %.1f \t %.f \t\t %d \t\t\t %d ",LF_fl,PF1,P_fl,t_fl,Energy_fl);
printf(" \n\t\t%d \t %.1f \t %.f \t\t %d \t\t\t %d ",LF_4,PF4,P_4,t4,Energy_4);
printf(" \n _____________________________________________________________________________________");
printf(" \n Total energy required by load for 24hour period (excluding 2hrs at no-load) = %d ",W_out_total);
printf(" \n _____________________________________________________________________________________\n\n");
printf(" \n d: All-day efficiency = %.1f percent",eta);
|