+//Chapter 7
+//Example 7.6
+//page 268
+//To calculate the loss formula coefficients of the system
+clear;clc;
+
+Ia=2-%i*0.5; Ic=1-%i*0.25;
+Ib=1.6-%i*0.4; Id=3.6-%i*0.9;
+Za=0.015+%i*0.06; Zc=0.01+%i*0.04;
+Zb=0.015+%i*0.06; Zd=0.01+%i*0.04;
+
+ID=Id+Ic ;//total load current
+
+//calculation of current distribution factors
+printf('\nCurrent distribution factors are :\n')
+Ma1=(ID/ID);
+Ma2=(0/ID);
+Mb1=(-Ic/ID);
+Mb2=(Id/ID);
+Mc1=(Ic/ID);
+Mc2=(Ic/ID);
+Md1=(Id/ID);
+Md2=(Id/ID);
+printf('Ma1=%d\tMb1=%0.4f\tMc1=%0.4f\tMd1=%0.4f\nMa2=%d\tMb2=%0.4f\tMc2=%0.4f\tMd2=%0.4f',Ma1,Mb1,Mc1,Md1,Ma2,Mb2,Mc2,Md2);
+
+//bus voltage calcultion
+[V1_mag,V1_ang]=polar(1.0+Ia*Za);
+[V2_mag,V2_ang]=polar(1+Ib*Zb);
+V1_ang=real(V1_ang)*180/%pi;
+V2_ang=real(V2_ang)*180/%pi;
+printf('\n\nBus voltages are given by \nV1=%0.3f @ %0.2fdeg PU\tV2=%0.3f @ %0.2fdeg PU',V1_mag,V1_ang,V2_mag,V2_ang);
+
+//current phase angles at the plants
+sigma1=atand(imag(Ia)/real(Ia));
+sigma2=atand(imag(Ib+Ic)/real(Ib+Ic));
+printf('\n\nCurrent phase angles at the plants\nSigma1=%ddeg\tSigma2=%ddeg',sigma1,sigma2);
+
+//plant power factors
+pf1=cosd(V1_ang-sigma1);
+pf2=cosd(V2_ang-sigma2);
+printf('\n\nThe plant power factors are\npf1=%0.4f\tpf2=%0.4f',pf1,pf2);
+
+//calculation of loss coefficients
+B11=(Ma1*Ma1*real(Za)+Mb1*Mb1*real(Zb)+Mc1*Mc1*real(Zc)+Md1*Md1*real(Zd))/(V1_mag*V1_mag*pf1*pf1);
+B22=(Ma2*Ma2*real(Za)+Mb2*Mb2*real(Zb)+Mc2*Mc2*real(Zc)+Md2*Md2*real(Zd))/(V2_mag*V2_mag*pf2*pf2);
+B12=(Ma1*Ma2*real(Za)+Mb1*Mb2*real(Zb)+Mc1*Mc2*real(Zc)+Md1*Md2*real(Zd))/(V1_mag*V2_mag*pf1*pf2);
+printf('\n\nThe Loss coefficients in PU are \nB11=%0.5f pu\nB22=%0.5f pu\nB12=%0.5f pu',B11,B22,B12);
+printf('\n\nThe Loss coefficients in reciprocal megawatts are \nB11=%0.8f MW^-1\nB22=%0.8f MW^-1\nB12=%0.8f MW^-1',B11/100,B22/100,B12/100);
diff --git a/83/CH7/EX7.6/result_example_7_6.txt b/83/CH7/EX7.6/result_example_7_6.txt
new file mode 100755
index 000000000..d4cd7f23f
--- /dev/null
+++ b/83/CH7/EX7.6/result_example_7_6.txt
@@ -0,0 +1,25 @@
+
+
+Current distribution factors are :
+Ma1=1 Mb1=-0.2174 Mc1=0.2174 Md1=0.7826
+Ma2=0 Mb2=0.7826 Mc2=0.2174 Md2=0.7826
+
+Bus voltages are given by
+V1=1.066 @ 6.06deg PU V2=1.052 @ 4.91deg PU
+
+Current phase angles at the plants
+Sigma1=-14deg Sigma2=-14deg
+
+The plant power factors are
+pf1=0.9391 pf2=0.9458
+
+The Loss coefficients in PU are
+B11=0.02226 pu
+B22=0.01595 pu
+B12=0.00406 pu
+
+The Loss coefficients in reciprocal megawatts are
+B11=0.00022259 MW^-1
+B22=0.00015947 MW^-1
+B12=0.00004062 MW^-1
+