+//(12.13) Air at 38C and 10% relative humidity enters an evaporative cooler with a volumetric flow rate of 140 m3/min. Moist air exits the cooler at 21C. Water is added to the soaked pad of the cooler as a liquid at 21C and evaporates fully into the moist air. There is no heat transfer with the surroundings and the pressure is constant throughout at 1 atm. Determine (a) the mass flow rate of the water to the soaked pad, in lb/h, and (b) the relative humidity of the moist air at the exit to the evaporative cooler.
+
+//solution
+
+//variable initialization
+T1 = 38 //temperature of entering air in degree celcius
+psi1 = .1 //relative humidity of entering air
+AV1 = 140 //volumetric flow rate of entering air in m^3/min
+Tw = 21 //temperature of added water in degree celcius
+T2 = 21 //temperature of exiting moist air in degree celcius
+p = 1 //pressure in atm
+
+//part(a)
+//from table A-2
+pg1 = .066 //in bar
+pv1 = psi1*pg1 //the partial pressure of the moist air entering the control volume in bar
+omega1 = .622*[pv1/(p*1.01325-pv1)]
+//The specific volume of the dry air can be evaluated from the ideal gas equation of state. The result is
+va1 = .887 //in m^3/kg
+cpa = 1.005
+madot = AV1/va1 //mass flow rate of the dry air in kg/min
+//from table A-2
+hf = 88.14
+hg1 = 2570.7
+hg2 = 2539.94
+
+omega2 = [cpa*(T1-T2)+omega1*(hg1-hf)]/(hg2-hf)
+mwdot = madot*60*(omega2-omega1) //in kg/h
+printf('the mass flow rate of the water to the soaked pad in kj/h is: %f',mwdot)
+
+//part(b)
+pv2 = (omega2*p*1.01325)/(omega2+.622) //in bars
+//At 21C, the saturation pressure is
+pg2 = .02487
+psi2 = pv2/pg2
+printf('\n the relative humidity of the moist air at the exit to the evaporative cooler is: %f',psi2)
+
+
+
+
+
+
+
+
+