diff --git a/416/CH13/EX13.2/example13_2.sce b/416/CH13/EX13.2/example13_2.sce new file mode 100755 index 000000000..358cca267 --- /dev/null +++ b/416/CH13/EX13.2/example13_2.sce @@ -0,0 +1,23 @@ +clc
+clear
+disp('example 13.2')
+pa1=20000 ;pa2=30000 //kva in in 3 ph power
+va1=11 ;va2=11 //voltage in kilo volts
+pt1=20000 ;pt2=30000//kva of 3 ph transformer
+vpt1=11 ;vpt2=11//voltage of primery of transformer
+vst1=132 ;vst2=132//voltage of secondary of transformer
+xg1=0.5 ;xg2=0.65 //reactance of generator
+xt1=0.05 ;xt2=0.05 //reactance of transformer with their own kva
+pb=pa2;vbg=va2;vbt=vpt2;//assumeing base quantoties
+xtn1=xt1*pb/pa1 ;xtn2=xt2*pb/pa2 //transformer reactance with new base
+xgn1=xg1*pb/pa1;xgn2=xg2*pb/pa2
+xn1=xtn1+xgn1;xn2=xtn2+xgn2 //reactancee up to fault from each generator
+xn=(xn1*xn2)/(xn1+xn2) //equalent reactance between generator and fault
+sckva=pb/xn ; //short circuit KVA
+disp('(a)')
+printf(" equivalent reactance is %.4f p.u \n short circuit KVA %dKVA",xn,sckva)
+disp('(b)')
+sccb=sckva/(vst1*sqrt(3))
+sccg1=sccb*(xn2/(xn1+xn2))*vst1/vpt1
+sccg2=sccb*(xn1/(xn1+xn2))*vst2/vpt2
+printf(" short circuit current on bus bar side %.1fA \n short circuit current of generator 1 is %.1fA \n short circuit current of generator 2 is %.1fA \n",sccb,sccg1,sccg2)
|