@@ -0,0 +1,28 @@
+//Electric Power Generation, Transmission and Distribution by S.N.Singh
+//Publisher:PHI Learning Private Limited
+//Year: 2012 ; Edition - 2
+//Example 19.1
+//Scilab Version : 6.0.0 ; OS : Windows
+
+clc;
+clear;
+
+
+V=132; //Operating Voltage in kV
+C=0.2; //Line to Ground Capacitance in microFarad
+f=50; //Supply Frequency in Hz
+L=1/(3*(2*%pi*f)^(2)*C*10^(-6)); //Inductance of Coil in H
+VA_coil=(132e3/1.732)^(2)/(2*%pi*f*L); //Rating of Coil in VA
+KVA_coil=VA_coil/1e3; //To convert VA value into kVA value
+
+printf("\nThe value of inductance of arc suppressor coil is %.2f H",L);
+printf("\nThe KVA rating of coil is %.3e kVA",KVA_coil);
+
+
+
+
+
+
+
+
+