diff options
Diffstat (limited to '3878/CH23/EX23.2/Ex23_2.sce')
-rw-r--r-- | 3878/CH23/EX23.2/Ex23_2.sce | 31 |
1 files changed, 31 insertions, 0 deletions
diff --git a/3878/CH23/EX23.2/Ex23_2.sce b/3878/CH23/EX23.2/Ex23_2.sce new file mode 100644 index 000000000..40bfa219b --- /dev/null +++ b/3878/CH23/EX23.2/Ex23_2.sce @@ -0,0 +1,31 @@ +clear +//Variable declaration +T_d1=21// The dry bulb temperature of air in °C +H=45// % saturation +T_d2=27// The dry bulb temperature of air in °C +T_wb1=20// The wet bulb temperature of air in °C +m=1.35// The mass flow rate of air in kg/s +C_pa=1.006// The specific heat capacity of air in kJ/kg.K +C_pw=4.187// The specific heat capacity of water in kJ/kg.K + +//Calculation + // 1.Total heat: +h_2=57.00// Enthalpy at 27°C DB, 20°C WB in kJ/kg +h_1=39.08// Enthalpy at 21°C DB, 45% sat in kJ/kg +dh=17.92// Heat to be removed in kJ/kg +Q_t=dh*m// Total heat in kW +printf("\n Total heat,Q_t=%2.1f kW", Q_t) + + +// 2.Latent heat: +x_2=0.0117// Moisture at 27°C DB, 20°C WB in kg/kg +x_1=0.0070// Moisture at 21°C DB, 45% sat in kg/kg +dx=x_2-x_1// Moisture to be removed in kg/kg +Q_l=dx*m*2440// Latent heat in kW +printf("\n Latent heat,Q_l=%2.1f kW", Q_l) + + +// 3.Sensible heat: +Q_s=(C_pa+((C_pw*x_2)))*(T_d2-T_d1)*m// Sensible heat in kW +printf("\n Sensible heat,Q_s=%1.1f kW", Q_s) + |