diff --git a/3872/CH14/EX14.3/EX14_3.sce b/3872/CH14/EX14.3/EX14_3.sce new file mode 100644 index 000000000..44b090683 --- /dev/null +++ b/3872/CH14/EX14.3/EX14_3.sce @@ -0,0 +1,58 @@ +//Book - Power System: Analysis & Design 5th Edition
+//Authors - J. Duncan Glover, Mulukutla S. Sarma, and Thomas J. Overbye
+//Chapter - 14 ; Example 14.3
+//Scilab Version - 6.0.0 ; OS - Windows
+
+
+clc;
+clear;
+kV=13.8; //The sending end line voltage in kVolts
+Vsln=1.05*kV/sqrt(3); //The sending end voltage with 5% above rated in kVolts
+Rload=20; //The Wye connected load resistance in Ohm
+Xload=40*%i; //The Wye connected load inductive reactance in Ohm
+Xc=-40*%i; //The Wye connected capacitive reactance in Ohm
+Rline=3; //The line resistance in Ohm
+Xline=6*%i; //The line inductive reactance in Ohm
+Ztot1=Rline+Xline+(Rload*Xload/(Rload+Xload)); //The total impedance seen by source without capacitance in Ohm
+Iline1=Vsln/Ztot1; //The line current without shunt capacitor in kA
+Vdrop1=(Rline+Xline)*Iline1; //The voltage drop across the line without shunt capacitor in KVolts
+Vload1=Vsln-Vdrop1; //The voltage drop across the load without shunt capacitor in KVolts
+Pload1=3*abs(Vload1)^2/Rload; //The real power delivered to the load without shunt capacitor in MW
+Qload1=3*abs(Vload1)^2/abs(Xload); //The reactive power delivered to the load without shunt capacitor in MVAR
+pf1=cos((atan(Qload1/Pload1))); //The power factor of the load without shunt capacitor
+Pline1=3*abs(Iline1)^2*Rline; //The real power loss in the line without shunt capacitor in MW
+Qline1=3*abs(Iline1)^2*abs(Xline); //The reactive power loss in the line without shunt capacitor in MVAR
+Psource1=Pload1+Pline1; //The real power delivered by the source without shunt capacitor in MW
+Qsource1=Qload1+Qline1; //The reactive power delivered by the source without shunt capacitor in MVAR
+Ssource1=sqrt(Psource1^2+Qsource1^2); //The apparent power delivered by the source without shunt capacitor in MVA
+Ztot2=Rline+Xline+(1/(1/Rload+1/Xload+1/Xc)); //The total impedance seen by source with capacitance in Ohm
+Iline2=Vsln/Ztot2; //The line current with shunt capacitor in kA
+Vdrop2=(Rline+Xline)*Iline2; //The voltage drop across the line with shunt capacitor in KVolts
+Vload2=Vsln-Vdrop2; //The voltage drop across the load with shunt capacitor in KVolts
+Pload2=3*abs(Vload2)^2/Rload; //The real power delivered to the load with shunt capacitor in MW
+Qload2=3*abs(Vload2)^2/abs(Xload); //The reactive power delivered to the load with shunt capacitor in MVAR
+pf2=cos((atan(Qload2/Pload2))); //The power factor of the load with shunt capacitor
+Pline2=3*abs(Iline2)^2*Rline; //The real power loss in the line with shunt capacitor in MW
+Qline2=3*abs(Iline2)^2*abs(Xline); //The reactive power loss in the line with shunt capacitor in MVAR
+Qc=3*abs(Vload2)^2/abs(Xc); //The reactive power delivered by the shunt capacitor inb MVAR
+Psource2=Pload2+Pline2; //The real power delivered by the source with shunt capacitor in MW
+Qsource2=Qload2+Qline2-Qc; //The reactive power delivered by the source with shunt capacitor in MVAR
+Ssource2=sqrt(Psource2^2+Qsource2^2); //The apparent power delivered by the source with shunt capacitor in MVA
+printf('a. Without Capacitor');
+printf('\nThe magnitude of line current is %f kA and %f degree',abs(Iline1),atand(imag(Iline1)/real(Iline1)));
+printf('\nThe magnitude of voltage drop in the line is %f kV and %f degree',abs(Vdrop1),atand(imag(Vdrop1)/real(Vdrop1)));
+printf('\nThe magnitude of voltage drop in the load is %f kV and %f degree',abs(Vload1),atand(imag(Vload1)/real(Vload1)));
+printf('\nThe real and reactive power delivered to the three phase load is %f MW and %f MVAR',Pload1,Qload1);
+printf('\nThe load power factor is %f lagging',pf1);
+printf('\nThe real and reactive power losses in the line is %f MW and %f MVAR',Pline1,Qline1);
+printf('\nThe real power, reactive power and Apparent power delivered by the source is %f MW , %f MVAR and %f MVA',Psource1,Qsource1,Ssource1);
+printf('\n\n\nb. With Capacitor');
+printf('\nThe magnitude of line current is %f kA and %f degree',abs(Iline2),atand(imag(Iline2)/real(Iline2)));
+printf('\nThe magnitude of voltage drop in the line is %f kV and %f degree',abs(Vdrop2),atand(imag(Vdrop2)/real(Vdrop2)));
+printf('\nThe magnitude of voltage drop in the load is %f kV and %f degree',abs(Vload2),atand(imag(Vload2)/real(Vload2)));
+printf('\nThe real and reactive power delivered to the three phase load is %f MW and %f MVAR',Pload2,Qload2);
+printf('\nThe load power factor is %f lagging',pf2);
+printf('\nThe real and reactive power losses in the line is %f MW and %f MVAR',Pline2,Qline2);
+printf('\nThe reactive power delivered by the shunt capacitor bank is %f MVAR',Qc);
+printf('\nThe real power, reactive power and Apparent power delivered by the source is %f MW , %f MVAR and %f MVA',Psource2,Qsource2,Ssource2);
+ //The third part of this question cannot be executed in SCILAB because of its theoritical nature
|