+//Book - Power system: Analysisi & Design 5th Edition
+//Authors - J. Duncan Glover, Mulukutla S. Sarma, and Thomas J.Overbye
+//Chapter-11 ;Example 11.3
+//Scilab Version - 6.0.0; OS - Windows
+
+clc;
+clear;
+
+P=1.0 //Infinite bus received real power in per unit
+Vbus=1.0 //Infinite bus voltage in per unit
+pf=0.95 //Lagging power factor
+Xdt=0.30
+XTR=0.10
+X12=0.20
+X13=0.10
+X23=0.20
+
+Xeq=Xdt+XTR+(X12*(X13+X23))/(X12+(X13+X23)); //The equialent reactance between the machine internal voltage and infinite bus in per unit
+theta=acos(pf);
+I=(P/(Vbus*pf))*exp(-%i*theta); //Current into the infinite bus in per unit
+Ei=Vbus+(%i*Xeq)*I; //The machine internal voltage in per unit
+
+printf('The magnitude of he machine internal voltage in per unit is %.4f pu and its angle is %.4f degrees',abs(Ei),atand(imag(Ei),real(Ei)));
+