diff --git a/3681/CH5/EX5.3/Ex5_3.sce b/3681/CH5/EX5.3/Ex5_3.sce new file mode 100644 index 000000000..2c1bf0a53 --- /dev/null +++ b/3681/CH5/EX5.3/Ex5_3.sce @@ -0,0 +1,22 @@ +// Calculating the kVA output of a single phase transformer
+clc;
+disp('Example 5.3, Page No. = 5.78')
+// Given Data
+D = 0.4;// Distance between core centres (in meter)
+f = 50;// Frequency (in Hz)
+Bm = 1.2;// Flux density of core (in Wb per meter square)
+Kw = 0.27;// Window space factor
+s = 2.3;// Current density (in Ampere per mm square)
+R1 = 2.8;// Ratio of core height and distance between core centres
+R2 = 0.56;// Ratio of circumscribing circle and distance between core centres
+R3 = 0.7;// Ratio of net iron area and area of circumscribing circle
+// Calculation of the kVA output of a single phase transformer
+Hw = R1*D;// Core heightor window height (in meter)
+d = R2*D;// Diameter of circumscribing circle (in meter)
+Ww = D-d;// Width of window (in meter)
+Aw = Hw*Ww;// Area of window (in meter square)
+A = (%pi/4)*d*d;// Area of circumscribing circle (in meter square)
+Ai = R3*A;// Net iron area (in meter square)
+Q = 2.22*f*Bm*Kw*s*10^(6)*Aw*Ai*10^(-3);// kVA output of a single phase transformer
+disp(Q,'kVA output of a single phase transformer (kVA)=');
+//in book answer is 450 kVA. The answers vary due to round off error
|