+// Calculating the continuous rating of motor
+clc;
+disp('Example 4.35, Page No. = 4.67')
+// Given Data
+Psh = 37.5;// Power rating of motor (in kW)
+th = 30;// Time (in minuts)
+Th = 90;// Heating time constant (in minuts)
+// Calculation of the continuous rating of motor
+ph = 1/(1-%e^(-th/Th));// Heating overload ratio
+K = 0.7^(2);// Maximum efficiency occurs at 70% full load
+pm = ((K+1)*ph-K)^(1/2);// Mechanical overload ratio
+Pnom = Psh/pm;// Continuous rating of motor (in kW)
+disp(Pnom,'Continuous rating of motor (kW)=');
+//in book answer is 17.2 kW. The answers vary due to round off error
+