diff options
Diffstat (limited to '3574/CH5/EX5.19/EX5_19.sce')
-rw-r--r-- | 3574/CH5/EX5.19/EX5_19.sce | 41 |
1 files changed, 41 insertions, 0 deletions
diff --git a/3574/CH5/EX5.19/EX5_19.sce b/3574/CH5/EX5.19/EX5_19.sce new file mode 100644 index 000000000..47f9361b6 --- /dev/null +++ b/3574/CH5/EX5.19/EX5_19.sce @@ -0,0 +1,41 @@ +// Example 5.19 +// Computation of (a) Locked rotor current per phase and minimum locked rotor +// torque when starting (b) Locked rotor current per phase when motor is delta +// connected (c) Code letter +// Page No.233 + +clc; +clear all; +close; + +// Given data +V=460; // Rated Voltage +Z=0.547; // Locked rotor impedance +n=1750; // Speed of machine +hp=60; // Horsepower rating of device +f=60; // Frequency of motor + + +// (a) Locked rotor current per phase and minimum locked rotor torque +Vphase=V/sqrt(3); // Voltage/phase +Ilr1=Vphase/Z; // Locked rotor current/phase +Trated=hp*5252/(n); // Rated torque +Tlr=1.4*Trated; // Locked rotor torque +T2=Tlr*(Vphase/V)^2; + +// (b) Locked rotor current per phase when motor is delta connected +Ilr=V/Z; // Locked rotor current/phase +Il=Ilr*sqrt(3); // Line current + +// (c) Code letter +Slr=sqrt(3)*V*Il/1000; // Code letter at rated voltage +kVA=Slr/f; + +// Display result on command window + +printf("\n Locked rotor current per phase = %0.1f A",Ilr1); +printf("\n Minimum locked rotor torque = %0.0f lb-ft",T2); +printf("\n Locked rotor current per phase when motor is delta connected = %0.0f A ",Il); +printf("\n Code letter = %0.1f",kVA); + + |