+// A Texbook on POWER SYSTEM ENGINEERING
+// A.Chakrabarti, M.L.Soni, P.V.Gupta, U.S.Bhatnagar
+// DHANPAT RAI & Co.
+// SECOND EDITION
+
+// PART II : TRANSMISSION AND DISTRIBUTION
+// CHAPTER 2: CONSTANTS OF OVERHEAD TRANSMISSION LINES
+
+// EXAMPLE : 2.24 :
+// Page number 119-120
+clear ; clc ; close ; // Clear the work space and console
+
+// Given data
+V = 250.0 // Line voltage(V)
+f = 50.0 // Frequency(Hz)
+D = 1.5 // Distance of separation(m)
+d = 1.5/100 // Diameter of conductor(m)
+l = 50.0 // Length of line(km)
+
+// Calculations
+// Case(i)
+r = d/2 // Radius of conductor(m)
+e = 8.854*10**-12 // Constant ε_0
+C = %pi*e/log(D/r) // Capacitance(F/m)
+C_l = C*1000.0*l // Capacitance for entire length(F)
+C_lu = C_l*10.0**6 // Capacitance for entire length(μF)
+// Case(ii)
+I_charg = 2.0*%pi*f*C_l*V*1000.0 // Charging current(mA)
+
+// Results
+disp("PART II - EXAMPLE : 2.24 : SOLUTION :-")
+printf("\nCase(i) : Capacitance of the line, C = %.3f μF", C_lu)
+printf("\nCase(ii): Charging current, I_charg = %.2f mA", I_charg)