+// A Texbook on POWER SYSTEM ENGINEERING
+// A.Chakrabarti, M.L.Soni, P.V.Gupta, U.S.Bhatnagar
+// DHANPAT RAI & Co.
+// SECOND EDITION
+
+// PART IV : UTILIZATION AND TRACTION
+// CHAPTER 9: ELECTRIC TRACTION SYSTEMS AND POWER SUPPLY
+
+// EXAMPLE : 9.1 :
+// Page number 817-818
+clear ; clc ; close ; // Clear the work space and console
+
+// Given data
+L = 3.0 // Length of section ACB of rail(km)
+L_B_A = 2.0 // Distance of B from A(km)
+I_load = 350.0 // Loading(A/km)
+r_rail = 0.035 // Resistance of rail(ohm/km)
+r_feed = 0.03 // Resistance of negative feeder(ohm/km)
+
+// Calculations
+x_val = integrate('I_load*(L-x)','x',0,L_B_A)
+I = x_val/(L_B_A-0) // Current in negative feeder(A)
+x = L-(I/I_load) // Distance from feeding point(km)
+C = integrate('r_rail*I_load*x','x',0,x)
+V = r_feed*L_B_A*I // Voltage produced by negative booster(V)
+rating = V*I/1000 // Rating of the booster(kW)
+
+// Results
+disp("PART IV - EXAMPLE : 9.1 : SOLUTION :-")
+printf("\nMaximum potential difference between any two points of the rails, C = %.2f V", C)
+printf("\nRating of the booster = %.1f kW", rating)