@@ -0,0 +1,31 @@
+// A Texbook on POWER SYSTEM ENGINEERING
+// A.Chakrabarti, M.L.Soni, P.V.Gupta, U.S.Bhatnagar
+// DHANPAT RAI & Co.
+// SECOND EDITION
+
+// PART IV : UTILIZATION AND TRACTION
+// CHAPTER 1: INDUSTRIAL APPLICATIONS OF ELECTRIC MOTORS
+
+// EXAMPLE : 1.3 :
+// Page number 680-681
+clear ; clc ; close ; // Clear the work space and console
+
+// Given data
+V = 400.0 // IM voltage(V)
+s_fl = 5.0 // Full-load slip(%)
+I_fl = 20.0 // Full load current drawn from supply by IM(A)
+Z = 2.5 // Impedance per phase(ohm)
+I_max = 50.0 // Maximum current drawn(A)
+
+// Calculations
+V_phase = V/3**0.5 // Normal phase voltage(V)
+P = (100**2*I_max*Z/V_phase)**0.5 // Tapping to be provided to auto-transformer(%)
+I_s = I_max/(P/100) // Starting current taken by motor(A)
+T_s_fl = (I_s/I_fl)**2*s_fl/100 // Starting torque in terms of full-load torque
+T_s_fl_R = (I_max/I_fl)**2*s_fl/100 // Starting torque in terms of full-load torque when a resistor is used
+
+// Results
+disp("PART IV - EXAMPLE : 1.3 : SOLUTION :-")
+printf("\nTapping to be provided on an auto-transformer, P = %.1f percent", P)
+printf("\nStarting torque in terms of full-load torque, T_s = %.3f*T_fl ", T_s_fl)
+printf("\nStarting torque in terms of full-load torque if a resistor were used in series, T_s = %.4f*T_fl ", T_s_fl_R)