+// A Texbook on POWER SYSTEM ENGINEERING
+// A.Chakrabarti, M.L.Soni, P.V.Gupta, U.S.Bhatnagar
+// DHANPAT RAI & Co.
+// SECOND EDITION
+
+// PART III : SWITCHGEAR AND PROTECTION
+// CHAPTER 8: PROTECTION OF ALTERNATORS AND AC MOTORS
+
+// EXAMPLE : 8.7 :
+// Page number 626-627
+clear ; clc ; close ; // Clear the work space and console
+
+// Given data
+kV = 11.0 // Alternator voltage(kV)
+MVA = 5.0 // Alternator rating(MVA)
+X = 2.0 // Reactance per phase(ohm)
+ofb = 35.0 // Out-of-balance current(%)
+R_n = 5.0 // Resistance through which star point is earthed(ohm)
+
+// Calculations
+I_fl = MVA*1000/(3**0.5*kV) // Full load current(A)
+I_ofb = ofb/100*I_fl // Out-of-balance current(A)
+x = I_ofb*R_n*100/(kV*1000/3**0.5) // Portion of winding unprotected(%)
+protected = 100.0-x // Winding that is protected against earth faults(%)
+
+// Results
+disp("PART III - EXAMPLE : 8.7 : SOLUTION :-")
+printf("\nPercentage of winding that is protected against earth faults = %.2f percent", protected)