+// A Texbook on POWER SYSTEM ENGINEERING
+// A.Chakrabarti, M.L.Soni, P.V.Gupta, U.S.Bhatnagar
+// DHANPAT RAI & Co.
+// SECOND EDITION
+
+// PART III : SWITCHGEAR AND PROTECTION
+// CHAPTER 6: CIRCUIT BREAKER
+
+// EXAMPLE : 6.1 :
+// Page number 545
+clear ; clc ; close ; // Clear the work space and console
+
+// Given data
+f = 50.0 // Generator frequency(Hz)
+kV = 7.5 // emf to neutral rms voltage(kV)
+X = 4.0 // Reactance of generator & connected system(ohm)
+C = 0.01*10**-6 // Distributed capacitance(F)
+
+// Calculations
+// Case(a)
+v = 2**0.5*kV // Active recovery voltage i.e phase to neutral(kV)
+V_max_restrike = v*2 // Maximum restriking voltage i.e phase to neutral(kV)
+// Case(b)
+L = X/(2.0*%pi*f) // Inductance(H)
+f_n = 1/(2.0*%pi*(L*C)**0.5*1000) // Frequency of transient oscillation(kHZ)
+// Case(c)
+t = 1.0/(2.0*f_n*1000) // Time(sec)
+avg_rate = V_max_restrike/t // Average rate of rise of voltage upto first peak of oscillation(kV/s)
+
+// Results
+disp("PART III - EXAMPLE : 6.1 : SOLUTION :-")
+printf("\nCase(a): Maximum re-striking voltage(phase-to-neutral) = %.1f kV", V_max_restrike)
+printf("\nCase(b): Frequency of transient oscillation, f_n = %.1f kHz", f_n)
+printf("\nCase(c): Average rate of rise of voltage upto first peak of oscillation = %.f kV/s \n", avg_rate)
+printf("\nNOTE: Changes in the obtained answer from that of textbook is due to more approximation in the textbook")