+// A Texbook on POWER SYSTEM ENGINEERING
+// A.Chakrabarti, M.L.Soni, P.V.Gupta, U.S.Bhatnagar
+// DHANPAT RAI & Co.
+// SECOND EDITION
+
+// PART II : TRANSMISSION AND DISTRIBUTION
+// CHAPTER 14: LIGHTNING AND PROTECTION AGAINST OVERVOLTAGES DUE TO LIGHTNING
+
+// EXAMPLE : 14.1 :
+// Page number 382
+clear ; clc ; close ; // Clear the work space and console
+
+// Given data
+RI_072 = 72000.0 // Charactersistic of lightning arrester
+Z_c = 500.0 // Surge impedance(ohm)
+V = 500.0 // Surge voltage(kV)
+
+// Calculations
+// Case(a)
+V_a = 2.0*V // Voltage at the end of line at open-circuit(kV)
+ratio_a = V_a/V // Ratio of voltage when line in open-circuited
+// Case(b)
+I = V*1000/Z_c // Surge current(A)
+R = RI_072/(I)**0.72 // Resistance of LA(ohm)
+ratio_b = R/Z_c // Ratio of voltage when line is terminated by arrester
+
+// Results
+disp("PART II - EXAMPLE : 14.1 : SOLUTION :-")
+printf("\nCase(a): Ratio of voltages appearing at the end of a line when line is open-circuited = %.f", ratio_a)