diff options
Diffstat (limited to '3472/CH18/EX18.1/Example18_1.sce')
-rw-r--r-- | 3472/CH18/EX18.1/Example18_1.sce | 39 |
1 files changed, 39 insertions, 0 deletions
diff --git a/3472/CH18/EX18.1/Example18_1.sce b/3472/CH18/EX18.1/Example18_1.sce new file mode 100644 index 000000000..12a6b7a59 --- /dev/null +++ b/3472/CH18/EX18.1/Example18_1.sce @@ -0,0 +1,39 @@ +// A Texbook on POWER SYSTEM ENGINEERING
+// A.Chakrabarti, M.L.Soni, P.V.Gupta, U.S.Bhatnagar
+// DHANPAT RAI & Co.
+// SECOND EDITION
+
+// PART II : TRANSMISSION AND DISTRIBUTION
+// CHAPTER 11: LOAD FREQUENCY CONTROL AND LOAD SHARING OF POWER GENERATING SOURCES
+
+// EXAMPLE : 11.1 :
+// Page number 330
+clear ; clc ; close ; // Clear the work space and console
+funcprot(0)
+
+// Given data
+rating = 1000.0 // Rating of alternator(kW)
+load = 1600.0 // Total load(kW)
+X_fl = 100.0 // Full load speed regulation of alernator X(%)
+Y_fl = 104.0 // Full load speed regulation of alernator Y(%)
+X_nl = 100.0 // No load speed regulation of alernator X(%)
+Y_nl = 105.0 // No load speed regulation of alernator Y(%)
+
+// Calculations
+h = poly(0,"h")
+PB = (Y_nl-X_nl)-h
+PR = rating/(Y_nl-X_nl)*PB // Load shared by machine X(kW) in terms of h
+QQ = (Y_fl-X_fl)-h
+RQ = rating/(Y_fl-X_fl)*QQ // Load shared by machine Y(kW) in terms of h
+h_1 = roots(PR+RQ-load)
+PB_1 = (Y_nl-X_nl)-h_1
+PR_1 = rating/(Y_nl-X_nl)*PB_1 // Load shared by machine X(kW)
+QQ_1 = (Y_fl-X_fl)-h_1
+RQ_1 = rating/(Y_fl-X_fl)*QQ_1 // Load shared by machine Y(kW)
+load_cease = rating/(Y_nl-X_nl) // Y cease supply load(kW)
+
+// Results
+disp("PART II - EXAMPLE : 11.1 : SOLUTION :-")
+printf("\nLoad shared by machine X, PR = %.f kW", PR_1)
+printf("\nLoad shared by machine Y, RQ = %.f kW", RQ_1)
+printf("\nLoad at which machine Y ceases to supply any portion of load = %.f kW", load_cease)
|