+// A Texbook on POWER SYSTEM ENGINEERING
+// A.Chakrabarti, M.L.Soni, P.V.Gupta, U.S.Bhatnagar
+// DHANPAT RAI & Co.
+// SECOND EDITION
+
+// PART II : TRANSMISSION AND DISTRIBUTION
+// CHAPTER 10: POWER SYSTEM STABILITY
+
+// EXAMPLE : 10.16 :
+// Page number 304-305
+clear ; clc ; close ; // Clear the work space and console
+
+// Given data
+S = 1000.0 // Rating of generator(MVA)
+N = 1500.0 // Speed of alternator(r.p.m)
+WR_sq = 5.0*10**6 // WR^2(lb.ft^2)
+
+// Calculations
+H = 2.31*10**-10*WR_sq*N**2/S // Inertia constant(MJ/MVA)
+H_100 = H*1000.0/100 // Inertia constant on 100 MVA(MJ/MVA)
+
+// Results
+disp("PART II - EXAMPLE : 10.16 : SOLUTION :-")
+printf("\nValue of inertia constant, H = %.1f MJ/MVA", H)
+printf("\nValue of inertia constant in 100 MVA base, H = %.f MJ/MVA", H_100)