+// A Texbook on POWER SYSTEM ENGINEERING
+// A.Chakrabarti, M.L.Soni, P.V.Gupta, U.S.Bhatnagar
+// DHANPAT RAI & Co.
+// SECOND EDITION
+
+// PART II : TRANSMISSION AND DISTRIBUTION
+// CHAPTER 10: POWER SYSTEM STABILITY
+
+// EXAMPLE : 10.10 :
+// Page number 275-276
+clear ; clc ; close ; // Clear the work space and console
+
+// Given data
+E_1 = 1.1 // Sending end voltage(p.u)
+x_d1 = 1.0 // Reactance(p.u)
+x_T1 = 0.1 // Reactance(p.u)
+x_l1 = 0.4 // Reactance(p.u)
+x_l2 = 0.4 // Reactance(p.u)
+x_T2 = 0.1 // Reactance(p.u)
+E_2 = 1.0 // Receiving end voltage(p.u)
+x_d2 = 1.0 // Reactance(p.u)
+x_L = 1.0 // Shunt inductor reactance(p.u)
+x_C = 1.0 // Static capacitor reactance(p.u)
+delta = 30.0 // δ(°)
+
+// Calculations
+// Case(a)
+Z_1_a = x_d1+x_T1+(x_l1/2.0) // Reactance(p.u)
+X_1_a = %i*Z_1_a
+Z_2_a = x_T2+x_d2 // Reactance(p.u)
+X_2_a = %i*Z_2_a
+Z_3_a = -x_C // Reactance(p.u)
+X_3_a = %i*Z_3_a
+X_a = X_1_a+X_2_a+(X_1_a*X_2_a/X_3_a) // Transfer reactance(p.u)
+P_max_a = E_1*E_2/abs(X_a) // Maximum steady state power if static capacitor is connected(p.u)
+P_a = P_max_a*sind(delta) // Value of P(p.u)
+Q_a = (E_1*E_2/abs(X_a))*cosd(delta)-(E_2**2/abs(X_a)) // Value of Q(p.u)
+// Case(b)
+Z_1_b = x_d1+x_T1+(x_l1/2.0) // Reactance(p.u)
+X_1_b = %i*Z_1_b
+Z_2_b = x_T2+x_d2 // Reactance(p.u)
+X_2_b = %i*Z_2_b
+Z_3_b = x_L // Reactance(p.u)
+X_3_b = %i*Z_3_b
+X_b = X_1_b+X_2_b+(X_1_b*X_2_b/X_3_b) // Transfer reactance(p.u)
+P_max_b = E_1*E_2/abs(X_b) // Maximum steady state power if static capacitor is replaced by an inductive reactor(p.u)
+P_b = P_max_b*sind(delta) // Value of P(p.u)
+Q_b = (E_1*E_2/abs(X_b))*cosd(delta)-(E_2**2/abs(X_b)) // Value of Q(p.u)
+
+// Results
+disp("PART II - EXAMPLE : 10.10 : SOLUTION :-")
+printf("\nCase(a): Maximum steady state power if static capacitor is connected, P_max = %.3f p.u", P_max_a)
+printf("\n Value of P = %.3f p.u", P_a)
+printf("\n Value of Q = %.3f p.u", Q_a)
+printf("\nCase(b): Maximum steady state power if static capacitor is replaced by an inductive reactor, P_max = %.3f p.u", P_max_b)
+printf("\n Value of P = %.3f p.u", P_b)
+printf("\n Value of Q = %.4f p.u", Q_b)