diff --git a/3472/CH17/EX17.1/Example17_1.sce b/3472/CH17/EX17.1/Example17_1.sce new file mode 100644 index 000000000..358b50f6e --- /dev/null +++ b/3472/CH17/EX17.1/Example17_1.sce @@ -0,0 +1,26 @@ +// A Texbook on POWER SYSTEM ENGINEERING
+// A.Chakrabarti, M.L.Soni, P.V.Gupta, U.S.Bhatnagar
+// DHANPAT RAI & Co.
+// SECOND EDITION
+
+// PART II : TRANSMISSION AND DISTRIBUTION
+// CHAPTER 10: POWER SYSTEM STABILITY
+
+// EXAMPLE : 10.1 :
+// Page number 270
+clear ; clc ; close ; // Clear the work space and console
+
+// Given data
+Z = 0.1 // Impedance of transmission line(p.u)
+M = 0.3 // Stability margin
+X = 1.0 // Constant(p.u)
+
+// Calculations
+sin_delta_0 = 1-M // Sin(δ_0)
+delta_0 = asind(sin_delta_0) // δ_0(°)
+P_0 = X/Z*sin_delta_0 // Magnitude of P_0(p.u)
+
+// Results
+disp("PART II - EXAMPLE : 10.1 : SOLUTION :-")
+printf("\nOperating power angle, δ_0 = %.2f° ", delta_0)
+printf("\nP_0 = %.2f p.u", P_0)
|