diff --git a/3472/CH14/EX14.13/Example14_13.sce b/3472/CH14/EX14.13/Example14_13.sce new file mode 100644 index 000000000..b216b785d --- /dev/null +++ b/3472/CH14/EX14.13/Example14_13.sce @@ -0,0 +1,24 @@ +// A Texbook on POWER SYSTEM ENGINEERING
+// A.Chakrabarti, M.L.Soni, P.V.Gupta, U.S.Bhatnagar
+// DHANPAT RAI & Co.
+// SECOND EDITION
+
+// PART II : TRANSMISSION AND DISTRIBUTION
+// CHAPTER 7: UNDERGROUND CABLES
+
+// EXAMPLE : 7.13 :
+// Page number 219
+clear ; clc ; close ; // Clear the work space and console
+
+// Given data
+V = 11.0*10**3 // Line Voltage(V)
+f = 50.0 // Frequency(Hz)
+C_c = 3.7 // Measured capacitance(µF)
+
+// Calculations
+C_0 = 2*C_c // Capacitance(µF)
+I_ch = 2*%pi*f*C_0*V/3**0.5*10**-6 // Charging current per phase(A)
+
+// Results
+disp("PART II - EXAMPLE : 7.13 : SOLUTION :-")
+printf("\nCharging current drawn by a cable = %.2f A", I_ch)
|