+// Theory and Problems of Thermodynamics
+// Chapter 9
+// Air_water Vapor Mixtures
+// Example 12
+
+clear ;clc;
+
+//Given data
+RH1 = 0.3 // relative humidity of summer day atmospheric air
+T1 = 313.15 // Temperature of air in summer day in K
+V = 3 // evaporative cooler rate in m^3/s
+t = 10 // cooler operation time in hours
+M = 28.97 // molecular weight of air
+R = 8.314 // gas constant
+
+// data from psychometric chart for T = 40`C and RH = 0.3
+SH1 = 0.0135 // in kg H2O/kg air
+pw1 = 2.05 // in kPa
+// Follow the constant wet bulb temperature line(23`C) from that point
+// till it intersects with RH = 0.8
+SH2 = 0.0184 // in kg H2O/kg air
+T2 = 27.3 // in degree C
+
+ma = (101.325-pw1)*1e3*V*M/(R*1e3*T1)
+
+mw = ma*(SH2-SH1)
+
+q_wat = mw*3600*10 // quantity of water required for 10 hours in kg
+
+
+// Output Results
+mprintf('The temperature of the air leaving the cooler = %4.1f degree C' , T2);
+mprintf('\n The specific humidity of air leaving cooler = %4.4f kg H2O/kg air' , SH2);
+mprintf('\n Quantity of water required to operate cooler for 10 hours = %4.1f kg',q_wat);
|