diff --git a/1820/CH8/EX8.1/Example8_1.sce b/1820/CH8/EX8.1/Example8_1.sce new file mode 100755 index 000000000..ed8980a05 --- /dev/null +++ b/1820/CH8/EX8.1/Example8_1.sce @@ -0,0 +1,33 @@ +// ELECTRIC POWER TRANSMISSION SYSTEM ENGINEERING ANALYSIS AND DESIGN
+// TURAN GONEN
+// CRC PRESS
+// SECOND EDITION
+
+// CHAPTER : 8 : LIMITING FACTORS FOR EXTRA-HIGH AND ULTRAHIGH VOLTAGE TRANSMISSION
+
+// EXAMPLE : 8.1 :
+clear ; clc ; close ; // Clear the work space and console
+
+// GIVEN DATA
+m_0 = 0.90 ; // Irregularity factor
+p = 74 ; // Atmospheric pressure in Hg
+t = 10 ; // temperature in degree celsius
+D = 550 ; // Equilateral spacing b/w conductors in cm
+d = 3 ; // overall diameter in cm
+
+// CALCULATIONS
+// For case (a)
+r = d/2 ;
+delta = 3.9211 * p/( 273 + t ) ; // air density factor
+V_0_ph = 21.1 * delta * m_0 * r * log(D/r) ; // disruptive critical rms line voltage in kV/phase
+V_0 = sqrt(3) * V_0_ph ; // disruptive critical rms line voltage in kV
+
+// For case (b)
+m_v = m_0 ;
+V_v_ph = 21.1*delta*m_v*r*(1 + (0.3/sqrt(delta*r) )) * log(D/r) ; // visual critical rms line voltage in kV/phase
+V_v = sqrt(3)*V_v_ph ; // visual critical rms line voltage in kV
+
+// DISPLAY RESULTS
+disp("EXAMPLE : 8.1 : SOLUTION :-") ;
+printf("\n (a) Disruptive critical rms line voltage , V_0 = %.1f kV \n",V_0) ;
+printf("\n (b) Visual critical rms line voltage , V_v = %.1f kV \n",V_v) ;
|