summaryrefslogtreecommitdiff
path: root/1820/CH6/EX6.3
diff options
context:
space:
mode:
Diffstat (limited to '1820/CH6/EX6.3')
-rwxr-xr-x1820/CH6/EX6.3/Example6_3.sce28
1 files changed, 28 insertions, 0 deletions
diff --git a/1820/CH6/EX6.3/Example6_3.sce b/1820/CH6/EX6.3/Example6_3.sce
new file mode 100755
index 000000000..1e22f6b1c
--- /dev/null
+++ b/1820/CH6/EX6.3/Example6_3.sce
@@ -0,0 +1,28 @@
+// ELECTRIC POWER TRANSMISSION SYSTEM ENGINEERING ANALYSIS AND DESIGN
+// TURAN GONEN
+// CRC PRESS
+// SECOND EDITION
+
+// CHAPTER : 6 : DIRECT-CURRENT POWER TRANSMISSION
+
+// EXAMPLE : 6.3 :
+clear ; clc ; close ; // Clear the work space and console
+
+// GIVEN DATA
+V_d0 = 125 ; // voltage rating of bridge rectifier in kV
+V_dr0 = V_d0 ; // Max continuos no-load direct voltage in kV
+I = 1600 ; // current rating of bridge rectifier in A
+I_d = I ; // Max continuous current in A
+
+// CALCULATIONS
+// For case (a)
+S_B = 1.047 * V_d0 * I_d ; // 3-phase kVA rating of rectifier transformer
+
+// For case (b)
+// SINCE V_d0 = 2.34*E_LN
+E_LN = V_d0/2.34 ; // Wye side kV rating
+
+// DISPLAY RESULTS
+disp("EXAMPLE : 6.3 : SOLUTION :-") ;
+printf("\n (a) Three-phase kilovolt-ampere rating , S_B = %d kVA \n",S_B) ;
+printf("\n (b) Wye-side kilovolt rating , E_L-N = %.4f kV \n",E_LN) ;