@@ -0,0 +1,25 @@
+// ELECTRIC POWER TRANSMISSION SYSTEM ENGINEERING ANALYSIS AND DESIGN
+// TURAN GONEN
+// CRC PRESS
+// SECOND EDITION
+
+// CHAPTER : 5 : UNDERGROUND POWER TRANSMISSION AND GAS-INSULATED TRANSMISSION LINES
+
+// EXAMPLE : 5.4 :
+clear ; clc ; close ; // Clear the work space and console
+
+// GIVEN DATA
+C_a = 2 * 10^-6 ; // Capacitance b/w two conductors in F/mi
+l = 2 ; // length in mi
+f = 60 ; // Frequency in Hz
+V_L_L = 34.5 * 10^3 ; // Line-to-line voltage in V
+
+// CALCULATIONS
+C_a1 = C_a * l ; // Capacitance for total cable length in F
+C_N = 2 * C_a1 ; // capacitance of each conductor to neutral in F . From equ 5.56
+V_L_N = V_L_L/sqrt(3) ; // Line-to-neutral voltage in V
+I_c = 2 * %pi * f * C_N * (V_L_N) ; // Charging current of cable in A
+
+// DISPLAY RESULTS
+disp("EXAMPLE : 5.4 : SOLUTION :-") ;
+printf("\n Charging current of the cable , I_c = %.2f A \n",I_c) ;