diff --git a/1808/CH7/EX7.16/Chapter7_Exampl16.sce b/1808/CH7/EX7.16/Chapter7_Exampl16.sce new file mode 100644 index 000000000..885ea3638 --- /dev/null +++ b/1808/CH7/EX7.16/Chapter7_Exampl16.sce @@ -0,0 +1,37 @@ +clc
+clear
+//INPUT DATA
+t1=30;//dry bulb temperature in Degree c
+t2=25;//Coil cooling temperature in Degree C
+x1=0.6;//realtive humidity in percentage
+t3=10;//Coil cooling temperature in Degree C
+x=0.2;//bypass factor
+Ra=287.3;//gas constant
+p=760;//pressure in mm of Hg
+V1=80;//volume in m^3/kg d.a
+ps1=31.81;//Saturation pressure in mm Hg
+cp=1.005;//specific pressure
+ps2=23.74;//Saturation pressure in mm Hg
+pv3=9.196;//Saturation pressure in mm Hg
+
+
+//CALCULATIONS
+v1=Ra*(273+t1)/((p-19.08)*133.5);//volume in m^3/kg d.a.
+ma=V1/v1;//Mass of dry air entering the coil in kg d.a./min
+pv1=x1*ps1;//Saturation pressure in mm Hg
+w1=0.622*(pv1/(p-pv1));//Specific humidity in kg w.v./kg d.a
+h1=cp*t1+w1*(2500+1.88*t1);//Enthalpy of air per kg of dry air in kJ/kg d.a.
+h2=cp*t2+w1*(2500+1.88*t2);//Enthalpy of air per kg of dry air in kJ/kg d.a.
+Rc1=ma*(h1-h2);//Capacity of the coil in TR
+x2=(pv1/ps2)*100;//realtive humidity in percentage
+t2r=x*(t1-t3)+t3;//Temperature at refrigeration in Degree c
+w3=0.622*(pv3/(p-pv3));//Specific humidity in kg w.v./kg d.a
+h3=cp*t3+w3*(2500+1.88*t3);//Enthalpy of air per kg of dry air in kJ/kg d.a.
+h2r=x*(h1-h3)+h3;//Enthalpy of air per kg of dry air in kJ/kg d.a.
+Rc2=ma*(h1-h2r);//Capacity of the coil in TR
+w2=x*(w1-w3)+w3;//Specific humidity in kg w.v./kg d.a
+mw=ma*(w1-w2);//Condensate flow in kg w.v./min
+
+//OUTPUT
+printf('CASE I \n (a1)Refrigeration required is %3.2f kJ/min \n (b1)Final RH is %3.3f percentage \n CASE II \n (a2)Refrigeration required is %3.2f kJ/min \n (b2)condensate flow is %3.4f kg w.v./min ',Rc1,x2,Rc2,mw)
+
|