diff --git a/1775/CH6/EX6.11/Chapter6_Example11.sce b/1775/CH6/EX6.11/Chapter6_Example11.sce new file mode 100755 index 000000000..96dbc4ae9 --- /dev/null +++ b/1775/CH6/EX6.11/Chapter6_Example11.sce @@ -0,0 +1,35 @@ +//Chapter-6, Illustration 11, Page 317
+//Title: Refrigeration cycles
+//=============================================================================
+clc
+clear
+
+//INPUT DATA
+T1=-18;//Temperature at point 1 in oC
+T3=27;//Temperature at point 3 in oC
+rp=4;//Pressure ratio
+m=0.045;//mass flow rate in kg/s
+y=1.4;//Ratio of specific heats
+Cp=1.005;//Specific heat at constant pressure in kJ/kg-K
+
+//CALCULATIONS
+x=(y-1)/y;//Ratio
+T2=(rp^x)*(273+T1);//Temperature at point 2 in K
+Tmax=T2-273;//Maximum temperature in oC
+T4=((1/rp)^x)*(273+T3);//Temperature at point 4 in K
+Tmin=T4-273;//Minimum temperature in oC
+qL=Cp*(T1-Tmin);//Heat rejected
+Wcin=Cp*(Tmax-T1);//Compressor work
+Wtout=Cp*(T3-Tmin);//Turbine work
+Wnet=Wcin-Wtout;//Net work done
+COP=qL/Wnet;//Co-efficient of performance
+Qref=m*qL;//Rate of refrigeration in kW
+
+//OUTPUT
+mprintf('Maximum temperature in the cycle is %3.0foC \n Minimum temperature in the cycle is %3.0foC \n COP is %3.2f \n Rate of refrigeration is %3.2f kW',Tmax,Tmin,COP,Qref)
+
+
+
+
+
+//==============================END OF PROGRAM=================================
|