diff --git a/1092/CH12/EX12.12/Example12_12.sce b/1092/CH12/EX12.12/Example12_12.sce new file mode 100755 index 000000000..43c9ef617 --- /dev/null +++ b/1092/CH12/EX12.12/Example12_12.sce @@ -0,0 +1,101 @@ +// Electric Machinery and Transformers
+// Irving L kosow
+// Prentice Hall of India
+// 2nd editiom
+
+// Chapter 12: POWER,ENERGY,AND EFFICIENCY RELATIONS OF DC AND AC DYNAMOS
+// Example 12-12
+
+clear; clc; close; // Clear the work space and console.
+
+// Given data
+// 3-phase Y-connected alternator
+kVA = 100 ; // kVA rating of the alternator
+V = 1100 ; // Rated voltage of the alternator in volt
+I_a_nl = 8 ; // No-load armature current in A
+P_in_nl = 6000 ; // No-load Power input to the armature in W
+V_oc = 1350 ; // Open-ckt line voltage in volt
+I_f = 18 ; // Field current in A
+V_f = 125 ; // voltage across field winding in volt
+
+// Calculations
+// From Ex.6-4,
+R_a = 0.45 ; // Armature resistance in ohm/phase
+I_a_rated = 52.5 ; // Rated armature current in A/phase
+
+// case a
+P_r = P_in_nl - 3 * (I_a_nl)^2 * R_a ; // Rotational loss of synchronous dynamo in W
+
+// case b
+P_f = V_f*I_f ; // Field copper loss in W
+
+// case c
+P_k = P_r + P_f ; // Fixed losses in W at rated synchronous speed
+Pk = P_k / 1000 ; // Fixed losses in kW at rated synchronous speed
+
+// case d
+P_cu = 3 * (I_a_rated)^2 * R_a ; // Rated electric armature cu-loss in W
+P_cu_kW = P_cu / 1000 ; // Rated electric armature cu-loss in kW
+
+LF1 = 1/4 ; // Load fraction
+LF2 = 1/2 ; // Load fraction
+LF3 = 3/4 ; // Load fraction
+P_cu_LF1 = P_cu * (LF1)^2 ; // Electric armature cu-loss in W at 1/4 load
+P_cu_LF2 = P_cu * (LF2)^2 ; // Electric armature cu-loss in W at 1/2 load
+P_cu_LF3 = P_cu * (LF3)^2 ; // Electric armature cu-loss in W at 3/4 load
+
+P_cu_LF1_kW = P_cu_LF1 / 1000 ; // Electric armature cu-loss in kW at 1/4 load
+P_cu_LF2_kW = P_cu_LF2 / 1000 ; // Electric armature cu-loss in kW at 1/2 load
+P_cu_LF3_kW = P_cu_LF3 / 1000 ; // Electric armature cu-loss in kW at 3/4 load
+
+
+// case e
+PF = 0.9 ; // Power factor lagging
+// Efficiency
+// η = LF(rated kVA)*PF / ( LF(rated kVA)*PF + P_k + P_cu ) * 100
+eta_1 = (LF1 * kVA * PF) / ( (LF1 * kVA * PF) + Pk + P_cu_LF1_kW ) * 100 ;// Efficiency at 1/4 load
+eta_2 = (LF2 * kVA * PF) / ( (LF2 * kVA * PF) + Pk + P_cu_LF2_kW ) * 100 ;// Efficiency at 1/2 load
+eta_3 = (LF3 * kVA * PF) / ( (LF3 * kVA * PF) + Pk + P_cu_LF3_kW ) * 100 ;// Efficiency at 3/4 load
+eta_fl = (kVA * PF) / ( (kVA * PF) + Pk + P_cu_kW ) * 100 ;// Efficiency at full load
+
+// case f
+Ia = sqrt(P_k/(3*R_a)); // Armature current in A for max.efficiency at 0.9 PF lagging
+LF = Ia / I_a_rated ; // Load fraction for max.efficiency
+// at max.efficiency P_cu = P_k
+eta_max = (LF * kVA * PF) / ( (LF * kVA * PF) + 2*Pk ) * 100 ;// Max Efficiency 0.9 PF lagging
+
+// case g
+P_o = kVA*PF ; // Output power at 0.9 PF lagging
+I_a = I_a_rated ;
+P_d = P_o + (3*(I_a)^2*R_a/1000) + (V_f*I_f/1000) ; // Armature power developed in kW at 0.9 PF lagging at full-load
+
+// Display the results
+disp("Example 12-12 Solution : ");
+
+printf(" \n From Ex.6-4,\n R_a = %.2f Ω/phase",R_a);
+printf(" \n I_a(rated) = %.1f A \n ",I_a_rated);
+
+printf(" \n a: Rotational loss of synchronous dynamo :\n P_r = %.f W \n",P_r);
+
+printf(" \n b: Field copper loss :\n P_f = %d W \n ",P_f);
+
+printf(" \n c: Fixed losses at rated synchronous speed :\n P_k = %.f W\n",P_k);
+
+printf(" \n d: P_cu at rated load = %.f W\n P_cu ,",P_cu);
+printf(" \n at %.2f rated load = %.1f W",LF1 , P_cu_LF1);
+printf(" \n at %.2f rated load = %.1f W",LF2 , P_cu_LF2);
+printf(" \n at %.2f rated load = %.1f W \n",LF3 , P_cu_LF3);
+
+
+printf(" \n e: Efficiency :\n η at %.2f load = %.1f percent",LF1,eta_1);
+printf(" \n η at %.2f load = %.1f percent",LF2,eta_2);
+printf(" \n η at %.2f load = %.1f percent",LF3,eta_3);
+printf(" \n η at full-load = %.1f percent \n",eta_fl);
+
+printf(" \n f: Armature current for max.efficiency at 0.9 PF lagging :");
+printf(" \n I_a(max) = %f A ≃ %.1f A\n",Ia,Ia);
+printf(" \n L.F. = %.2f \n",LF);
+printf(" \n Maximum efficiency :\n η_max = %.1f percent \n ",eta_max);
+
+printf(" \n g: Armature power developed at 0.9 PF lagging at full-load :");
+printf(" \n P_d = %.2f kW ",P_d);
|