diff options
author | prashantsinalkar | 2017-10-10 12:27:19 +0530 |
---|---|---|
committer | prashantsinalkar | 2017-10-10 12:27:19 +0530 |
commit | 7f60ea012dd2524dae921a2a35adbf7ef21f2bb6 (patch) | |
tree | dbb9e3ddb5fc829e7c5c7e6be99b2c4ba356132c /3760/CH1/EX1.48 | |
parent | b1f5c3f8d6671b4331cef1dcebdf63b7a43a3a2b (diff) | |
download | Scilab-TBC-Uploads-7f60ea012dd2524dae921a2a35adbf7ef21f2bb6.tar.gz Scilab-TBC-Uploads-7f60ea012dd2524dae921a2a35adbf7ef21f2bb6.tar.bz2 Scilab-TBC-Uploads-7f60ea012dd2524dae921a2a35adbf7ef21f2bb6.zip |
initial commit / add all books
Diffstat (limited to '3760/CH1/EX1.48')
-rw-r--r-- | 3760/CH1/EX1.48/Ex1_48.sce | 18 |
1 files changed, 18 insertions, 0 deletions
diff --git a/3760/CH1/EX1.48/Ex1_48.sce b/3760/CH1/EX1.48/Ex1_48.sce new file mode 100644 index 000000000..f0b27a94f --- /dev/null +++ b/3760/CH1/EX1.48/Ex1_48.sce @@ -0,0 +1,18 @@ +clc;
+P=400000; // rated KVA of transformer
+P1=11000; // rated primary voltage
+S2=6600; // rated secondary voltage
+v1=360; // voltage recorded during short circuit of l v winding for first transformer
+p1=3025; // power dissipated during short circuit of l v winding for first transformer
+v2=400; // voltage recorded during short circuit of l v winding for second transformer
+p2=3200; // power dissipated during short circuit of l v winding for second transformer
+v3=480; // voltage recorded during short circuit test of l v winding third transformer
+p3=3250; // power dissipated during short circuit of l v winding for third transformer
+l1=(P+(v1/v2)*P+(v1/v3)*P)/1000;
+printf('The greatest load that can be put on the transformers is %f KVA\n',l1);
+is=P/S2; // secondary rated current
+// transformer 1 is fully loaded , its carries full load current
+re2=p1/is^2; // total resistance referred to secondary side
+vd=is*re2; // voltage drop for transformer 1
+E2=S2-vd;
+printf('Secondary terminal voltage is %f v',E2);
|