diff --git a/3472/CH9/EX9.26/Example9_26.sce b/3472/CH9/EX9.26/Example9_26.sce new file mode 100644 index 000000000..d8acc46e2 --- /dev/null +++ b/3472/CH9/EX9.26/Example9_26.sce @@ -0,0 +1,25 @@ +// A Texbook on POWER SYSTEM ENGINEERING
+// A.Chakrabarti, M.L.Soni, P.V.Gupta, U.S.Bhatnagar
+// DHANPAT RAI & Co.
+// SECOND EDITION
+
+// PART II : TRANSMISSION AND DISTRIBUTION
+// CHAPTER 2: CONSTANTS OF OVERHEAD TRANSMISSION LINES
+
+// EXAMPLE : 2.26 :
+// Page number 120
+clear ; clc ; close ; // Clear the work space and console
+
+// Given data
+d = 2.0 // Spacing between conductors(m)
+dia = 1.25/100 // Diameter of conductor(m)
+
+// Calculations
+r = dia/2 // Radius of conductor(m)
+e = 8.854*10**-12 // Constant ε_0
+C = 2*%pi*e/log(d/r) // Capacitance(F/m)
+C_u = C*1000*10.0**6 // Capacitance for entire length(μF/km)
+
+// Results
+disp("PART II - EXAMPLE : 2.26 : SOLUTION :-")
+printf("\nCapacitance of each line conductor, C = %.4f μF/km", C_u)
|