summaryrefslogtreecommitdiff
path: root/3472/CH28/EX28.1/Example28_1.sce
diff options
context:
space:
mode:
authorprashantsinalkar2017-10-10 12:27:19 +0530
committerprashantsinalkar2017-10-10 12:27:19 +0530
commit7f60ea012dd2524dae921a2a35adbf7ef21f2bb6 (patch)
treedbb9e3ddb5fc829e7c5c7e6be99b2c4ba356132c /3472/CH28/EX28.1/Example28_1.sce
parentb1f5c3f8d6671b4331cef1dcebdf63b7a43a3a2b (diff)
downloadScilab-TBC-Uploads-7f60ea012dd2524dae921a2a35adbf7ef21f2bb6.tar.gz
Scilab-TBC-Uploads-7f60ea012dd2524dae921a2a35adbf7ef21f2bb6.tar.bz2
Scilab-TBC-Uploads-7f60ea012dd2524dae921a2a35adbf7ef21f2bb6.zip
initial commit / add all books
Diffstat (limited to '3472/CH28/EX28.1/Example28_1.sce')
-rw-r--r--3472/CH28/EX28.1/Example28_1.sce36
1 files changed, 36 insertions, 0 deletions
diff --git a/3472/CH28/EX28.1/Example28_1.sce b/3472/CH28/EX28.1/Example28_1.sce
new file mode 100644
index 000000000..c1459da0e
--- /dev/null
+++ b/3472/CH28/EX28.1/Example28_1.sce
@@ -0,0 +1,36 @@
+// A Texbook on POWER SYSTEM ENGINEERING
+// A.Chakrabarti, M.L.Soni, P.V.Gupta, U.S.Bhatnagar
+// DHANPAT RAI & Co.
+// SECOND EDITION
+
+// PART III : SWITCHGEAR AND PROTECTION
+// CHAPTER 2: FAULT LIMITING REACTORS
+
+// EXAMPLE : 2.1 :
+// Page number 479-480
+clear ; clc ; close ; // Clear the work space and console
+
+// Given data
+kVA_A = 2500.0 // Rating of alternator A(kVA)
+x_A = 8.0 // Reactance of alternator A(%)
+kVA_B = 5000.0 // Rating of alternator B(kVA)
+x_B = 6.0 // Reactance of alternator B(%)
+kVA_CB = 150000.0 // Rating of circuit breaker(kVA)
+kVA_T = 10000.0 // Rating of transformer(kVA)
+x_T = 7.5 // Reactance of transformer(%)
+V = 3300.0 // System voltage(V)
+
+// Calculations
+kVA_base = 10000.0 // Base kVA
+X_A = kVA_base/kVA_A*x_A // Reactance of generator A(%)
+X_B = kVA_base/kVA_B*x_B // Reactance of generator B(%)
+X_eq = X_A*X_B/(X_A+X_B) // Combined reactance of A & B(%)
+kVA_SC_G = kVA_base/X_eq*100 // Short-circuit kVA due to generators(kVA)
+kVA_SC_T = kVA_base/x_T*100 // Short-circuit kVA due to grid supply(kVA)
+X = (kVA_base*100/(kVA_CB-kVA_SC_G))-x_T // Reactance necessary to protect switchgear(%)
+I_fl = kVA_base*1000/(3**0.5*V) // Full load current corresponding to 10000 kVA(A)
+X_phase = X*V/(3**0.5*I_fl*100) // Actual value of reactance per phase(ohm)
+
+// Results
+disp("PART III - EXAMPLE : 2.1 : SOLUTION :-")
+printf("\nReactance necessary to protect the switchgear = %.3f ohm/phase", X_phase)