summaryrefslogtreecommitdiff
path: root/2273/CH6/EX6.15
diff options
context:
space:
mode:
authorpriyanka2015-06-24 15:03:17 +0530
committerpriyanka2015-06-24 15:03:17 +0530
commitb1f5c3f8d6671b4331cef1dcebdf63b7a43a3a2b (patch)
treeab291cffc65280e58ac82470ba63fbcca7805165 /2273/CH6/EX6.15
downloadScilab-TBC-Uploads-b1f5c3f8d6671b4331cef1dcebdf63b7a43a3a2b.tar.gz
Scilab-TBC-Uploads-b1f5c3f8d6671b4331cef1dcebdf63b7a43a3a2b.tar.bz2
Scilab-TBC-Uploads-b1f5c3f8d6671b4331cef1dcebdf63b7a43a3a2b.zip
initial commit / add all books
Diffstat (limited to '2273/CH6/EX6.15')
-rwxr-xr-x2273/CH6/EX6.15/ex6_15.sce31
1 files changed, 31 insertions, 0 deletions
diff --git a/2273/CH6/EX6.15/ex6_15.sce b/2273/CH6/EX6.15/ex6_15.sce
new file mode 100755
index 000000000..e06a771f1
--- /dev/null
+++ b/2273/CH6/EX6.15/ex6_15.sce
@@ -0,0 +1,31 @@
+//Determine the induced voltage in the telephone line
+clear;
+clc;
+
+//soltion
+//given
+Vl=132*1000;//Volt
+P=28*10^6;//load in kw
+pf=0.85;//power factor
+f=50;//Hz
+l=200;//length of the line
+r=0.005;//radius of conductor
+hA=20;//height of the line
+Ao=4*sqrt(3)/2;
+dAP=Ao+5;
+dAQ=dAP+1;;
+dBP=sqrt(5*5+2*2);
+dBQ=sqrt(6*6+2*2);
+Ma=0.2*log(dAQ/dAP);
+Mb=0.2*log(dBQ/dBP);
+M=(Mb-Ma)*10^-3;
+I=P/(sqrt(3)*Vl*pf);
+Vm=2*%pi*f*M*I;
+printf("For 200 km line induced voltage= %.1f volts\n",Vm*l);
+Va=Vl/sqrt(3);
+Vb=Va;
+Vpa=Va*log((2*(hA+Ao)-dAP)/dAP)/log((2*(hA+Ao)-r)/r);
+Vpb=Vb*log((2*(hA+Ao)-dBP)/dBP)/log((2*(hA+Ao)-r)/r);
+Vp=Vpb-Vpa;
+printf("The potential of telephone line= %d volts",Vp);
+//the ans in the book is Vm= 90.4 volts and Vp=4396 because of using round off in some values