diff --git a/1775/CH6/EX6.17/Chapter6_Example17.sce b/1775/CH6/EX6.17/Chapter6_Example17.sce new file mode 100755 index 000000000..1699e40ee --- /dev/null +++ b/1775/CH6/EX6.17/Chapter6_Example17.sce @@ -0,0 +1,45 @@ +//Chapter-6, Illustration 17, Page 324
+//Title: Refrigeration cycles
+//=============================================================================
+clc
+clear
+
+//INPUT DATA
+T1=271;//Temperature at point 1 in K
+T=265;//Temperature at point 1' in K
+Ta=303;//Temperature at point 2' in K
+Cpv=0.733;//Specific heat of vapour in kJ/kg
+Cpl=1.235;//Specific heat of liquid in kJ/kg
+h=184.07;//Liquid enthalpy at T in kJ/kg
+s=0.7;//Entropy at point 1' in kJ/kg-K
+sa=0.685;//Vapour entropy at Ta in kJ/kg-K
+ha=199.62;//Enthalpy at point 2' in kJ/kg
+hfb=64.59;//Liquid enthalpy at Ta in kJ/kg
+DT3=5;//Temperature difference in oC
+Q=2532;//Refrigeration capacity in kJ/min
+
+//CALCULATIONS
+s2=s+(Cpv*((log(T1/T))/(log(2.718))));//Entropy at point 1 in kJ/kg-K
+h1=h+(Cpv*(T1-T));//Enthalpy at point 1 in kJ/kg-K
+T2=(2.718^((s2-sa)/Cpv))*Ta;//Temperature at point 2 in K
+h2=ha+(Cpv*(T2-Ta));//Enthalpy at point 2 in kJ/kg
+h4=hfb-(Cpl*DT3);//Enthalpy at point 4 in kJ/kg
+COP=(h1-h4)/(h2-h1);//Co-efficient of performance
+m=Q/(h1-h4);//Mass flow rate of refrigerant in kJ/min
+P=(m*(h2-h1))/(60*12);//Power required in kW/TR
+
+//OUTPUT
+mprintf('COP is %3.2f \n Theoretical power required per tonne of refrigeration is %3.3f kW/TR',COP,P)
+
+
+
+
+
+
+
+
+
+
+
+
+//==============================END OF PROGRAM=================================
|