1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
|
{
"metadata": {
"name": "",
"signature": "sha256:b792438c72450dcd6d934e54e6cfded0900e6de0fdddb69b36f4edb85bc5ee53"
},
"nbformat": 3,
"nbformat_minor": 0,
"worksheets": [
{
"cells": [
{
"cell_type": "heading",
"level": 1,
"metadata": {},
"source": [
"Chapter10-Air conditioning\n"
]
},
{
"cell_type": "heading",
"level": 2,
"metadata": {},
"source": [
"Ex1-pg293"
]
},
{
"cell_type": "code",
"collapsed": false,
"input": [
"import math\n",
"## Example 10.1\n",
"print('Example 10.1\\n\\n');\n",
"print('Page No. 293\\n\\n');\n",
"\n",
"## given\n",
"m = 1.;## mass flow rate of initial air mixture in kg/s\n",
"T = 23.5;## Initial temperature in degree celcius\n",
"m1 = 0.6;## Percentage of fresh air mixture\n",
"T1 = 5.;## Dry Bulb Temperature of fresh air in degree celcius\n",
"w1 = 0.005;## Humidity of fresh air at temperature T1 in kg/kg\n",
"m2 = 0.4;## Percentage of recirculated air mixture\n",
"T2 = 25.;## Dry Bulb Temperature of recirculated air in degree celcius\n",
"w2 = 0.015;## Humidity of recirculated air at temperature T2 in kg/kg\n",
"\n",
"##In air conditioning => m1*w1 + m2*w2 = m*w\n",
"w = (m1*w1 + m2*w2)/m;## in kg/kgs\n",
"print'%s %.2f %s'%('The humidity of the air mixture is ',w,' kg/kg \\n')\n",
"\n",
"##The specific enthalpy in J/kg can be calculated by the formula => h = (1.005*10^3*T) +(w*((2.50*10^6)+(1.86*10^3*T))); where the T is the temperature and w is the humidity at temperature T\n",
"h_f = (1.005*10**3*T1) +(w1*((2.50*10**6)+(1.86*10**3*T1)));## Specific enthalpy of fresh air in J/kg\n",
"h_r = (1.005*10**3*T2) +(w2*((2.50*10**6)+(1.86*10**3*T2)));## Specific enthalpy of recirculated air in J/kg\n",
"h_m = (1.005*10**3*T) +(w*((2.50*10**6)+(1.86*10**3*T)));## Specific enthalpy of final air mixture in J/kg\n",
"\n",
"h_t = (m1*h_f) + (m2*h_r);## Total enthalpy of initial air mixturein J/kg\n",
"Q = m*(h_m - h_t);## in Watts\n",
"print'%s %.2f %s'%('The load on the heater is ',Q,' W')\n",
"## Deviation in answer due to direct substitution and some approximation in answer in book\n",
"\n"
],
"language": "python",
"metadata": {},
"outputs": [
{
"output_type": "stream",
"stream": "stdout",
"text": [
"Example 10.1\n",
"\n",
"\n",
"Page No. 293\n",
"\n",
"\n",
"The humidity of the air mixture is 0.01 kg/kg \n",
"\n",
"The load on the heater is 10638.99 W\n"
]
}
],
"prompt_number": 1
},
{
"cell_type": "heading",
"level": 2,
"metadata": {},
"source": [
"Ex2-pg298"
]
},
{
"cell_type": "code",
"collapsed": false,
"input": [
"import math\n",
"## Example 10.2\n",
"print('Example 10.2\\n\\n');\n",
"print('Page No. 298\\n\\n');\n",
"\n",
"## given\n",
"m1 = 0.75;## Percentage of fresh air mixture\n",
"T1 = 31.;## Dry Bulb Temperature of fresh air in degree celcius\n",
"w1 = 0.0140;## Humidity of fresh air at temperature T1 in kg/kg\n",
"m2 = 0.75;## Percentage of recirculated air mixture\n",
"T2 = 22.;## Dry Bulb Temperature of recirculated air in degree celcius\n",
"w2 = 0.0080;## Humidity of recirculated air at temperature T2 in kg/kg\n",
"m = 1.50;## mass flow rate of final air mixture in kg/s\n",
"T = 10.;## Dew Point temperature in degree celcius\n",
"\n",
"##In air conditioning => m1*w1 + m2*w2 = m*w\n",
"w = (m1*w1 + m2*w2)/m## in kg/kgs\n",
"print'%s %.2f %s'%('The humidity of the air mixture is ',w,' kg/kg \\n')\n",
"\n",
"\n",
"## from the psychrometric chart, at w = 0.011kg/kg, the dry bulb temperature is = 26.5 degree celcius also the humidity of saturated air at 10 degree celcius is 0.0075kg/kg\n",
"T_w = 26.5;## Dry Bulb temerature in degree celcius\n",
"w_10 = 0.0075;## humidity at temperatue T in kg/kg\n",
"\n",
"##the specific enthalpy in J/kg can be calculated by the formula => h = (1.005*10^3*T) +(w*((2.50*10^6)+(1.87*10^3*T))); where the T is the temperature and w is the humidity at temperature T\n",
"\n",
"h_a = (1.005*10**3*T_w) +(w*((2.50*10**6)+(1.88*10**3*T_w)));## Specific enthalpy of recirculated air in J/kg\n",
"h_s = (1.005*10**3*T) +(w_10*((2.50*10**6)+(1.87*10**3*T)));## Specific enthalpy of saturated air at 10 degree celcius in J/kg\n",
"\n",
"Q = m*(h_a - h_s);## in Watts\n",
"print'%s %.2f %s'%('The cooling load on the washer is ',Q,' W')\n",
"## Answer wrongly calculated in the book\n"
],
"language": "python",
"metadata": {},
"outputs": [
{
"output_type": "stream",
"stream": "stdout",
"text": [
"Example 10.2\n",
"\n",
"\n",
"Page No. 298\n",
"\n",
"\n",
"The humidity of the air mixture is 0.01 kg/kg \n",
"\n",
"The cooling load on the washer is 38610.41 W\n"
]
}
],
"prompt_number": 2
}
],
"metadata": {}
}
]
}
|