//Chapter 10 //Example 10_5 //Page 236 clear;clc; kw=3600; pf=0.8; vs=33; r=5.31; x=5.54; //Sending end voltage per phase vsp=vs*1000/sqrt(3); printf("Sending end voltage per- phase = %d V \n", vsp); //line current il=kw/3*1000/pf; printf("Line current = %d*10^5/Vr \n", il/10^5); //using approximate expression, vr=18435; printf("(i) Vr = %d V \n", vr); lv=sqrt(3)*vr/1000; printf(" Line voltage at recieving end = %.2f kV \n\n", lv); //line current lc=il/vr; printf("(ii) Line current = %.2f A \n\n", lc); loss=3*lc^2*r; eff=kw/(kw+loss/1000); printf("(iii) Line losses = %.3f kW \n", loss/1000); printf(" Transmission efficiency = %.2f %% \n\n", eff*100)